Plan Review Notes
Plan Review Notes For Permit 19100889
Permit Number 19100889
Review Stop M
Sequence Number 2
Notes
Date Text
2020-02-05 14:17:002ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19100889
 2/5/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FIRE DEPARTMENT IS QUESTIONING THE OCCUPANCY
 CLASSIFICATION OF THE PROPOSED PROJECT AND REQUIRES
 MORE INFORMATION. CURRENTLY IS HAS BEEN CLASSIFIED AS A
 BUSINESS OCCUPANCY AS STATED ON SHEET A-1, HOWEVER THE
 PLANS INDICATE THE SPACE WILL BE USED FOR AUTO BODY
 REPAIR AND DETAILING AS STATED ON SHEET M1.1. IT
 APPEARS THEN IT WOULD BE AN S-1 STORAGE OCCUPANCY-
 REPAIR GARAGE. ACCORDING TO THE ENGINEER'S RESPONSE
 NARRATIVE TO 1ST REVIEW COMMENTS "THERE WILL BE NO
 MOTOR VEHICLE REPAIR OR OPERATION WITHIN THIS FACILITY;
 THE VEHICLES WILL BE MOVED USING DOLLIES INSTEAD" FOR
 THAT REASON HE HAS REMOVED THE CO/NO2 SENSORS AND IS
 CITING SECTION 502.14 EXCEPTION #3. A) THE EOR MUST
 PROVIDE THESE STATEMENTS FROM THE NARRATIVE ONTO THE
 PLAN. B) THE EOR AND/OR CONTRACTOR SHALL PROVIDE A
 SUBMITTAL FOR THE CAR DOLLIES WITH A REVIEW AND
 APPROVAL STAMP BY THE EOR- SECTION 107.2.1 WPB. IN
 ADDITION THE PLANS SHALL SHOW THE DESIGNATED STORAGE
 AREA FOR THE DOLLIES.
  
 2) THE EF-7 VENTILATION SYSTEM FOR THE DRIVE IN FRONT
 DRIVE-IN AREA HAS BEEN REMOVED FROM THE RESUBMITTED
 PLAN. PLEASE REPLACE THE SYSTEM AND UPDATE THE PLANS TO
 INCLUDE THE FAN SCHEDULE AND SEQUENCING- SECTION 502.14
 FBC M.
  
 3) REFER TO SECTION 406.8.2 FBC B AND LOCATE THE
 CONTROLS FOR THE MANUAL PURGE SYSTEMS TO THE ENTRANCES
 OF THE BUILDING.
  
 4) SHOW THE LOCATION ON THE PLANS WHERE AUTO BODY AND
 DETAILING MATERIALS WILL BE STORED. REFER TO SECTION
 414.1.3 AND PROVIDE A MATERIALS REPORT AND MSDS SHEETS.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  