| 2020-02-05 14:17:00 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19100889 |
| | 2/5/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE FIRE DEPARTMENT IS QUESTIONING THE OCCUPANCY |
| | CLASSIFICATION OF THE PROPOSED PROJECT AND REQUIRES |
| | MORE INFORMATION. CURRENTLY IS HAS BEEN CLASSIFIED AS A |
| | BUSINESS OCCUPANCY AS STATED ON SHEET A-1, HOWEVER THE |
| | PLANS INDICATE THE SPACE WILL BE USED FOR AUTO BODY |
| | REPAIR AND DETAILING AS STATED ON SHEET M1.1. IT |
| | APPEARS THEN IT WOULD BE AN S-1 STORAGE OCCUPANCY- |
| | REPAIR GARAGE. ACCORDING TO THE ENGINEER'S RESPONSE |
| | NARRATIVE TO 1ST REVIEW COMMENTS "THERE WILL BE NO |
| | MOTOR VEHICLE REPAIR OR OPERATION WITHIN THIS FACILITY; |
| | THE VEHICLES WILL BE MOVED USING DOLLIES INSTEAD" FOR |
| | THAT REASON HE HAS REMOVED THE CO/NO2 SENSORS AND IS |
| | CITING SECTION 502.14 EXCEPTION #3. A) THE EOR MUST |
| | PROVIDE THESE STATEMENTS FROM THE NARRATIVE ONTO THE |
| | PLAN. B) THE EOR AND/OR CONTRACTOR SHALL PROVIDE A |
| | SUBMITTAL FOR THE CAR DOLLIES WITH A REVIEW AND |
| | APPROVAL STAMP BY THE EOR- SECTION 107.2.1 WPB. IN |
| | ADDITION THE PLANS SHALL SHOW THE DESIGNATED STORAGE |
| | AREA FOR THE DOLLIES. |
| | |
| | 2) THE EF-7 VENTILATION SYSTEM FOR THE DRIVE IN FRONT |
| | DRIVE-IN AREA HAS BEEN REMOVED FROM THE RESUBMITTED |
| | PLAN. PLEASE REPLACE THE SYSTEM AND UPDATE THE PLANS TO |
| | INCLUDE THE FAN SCHEDULE AND SEQUENCING- SECTION 502.14 |
| | FBC M. |
| | |
| | 3) REFER TO SECTION 406.8.2 FBC B AND LOCATE THE |
| | CONTROLS FOR THE MANUAL PURGE SYSTEMS TO THE ENTRANCES |
| | OF THE BUILDING. |
| | |
| | 4) SHOW THE LOCATION ON THE PLANS WHERE AUTO BODY AND |
| | DETAILING MATERIALS WILL BE STORED. REFER TO SECTION |
| | 414.1.3 AND PROVIDE A MATERIALS REPORT AND MSDS SHEETS. |
| | A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL |
| | IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF |
| | HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED |
| | SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO |
| | SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION |
| | CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE |
| | METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT |
| | NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS |
| | AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE |
| | REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION |
| | AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON, |
| | FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL |
| | AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |