| Plan Review Notes For Permit 19100889 |
| Permit Number |
19100889 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-27 08:09:55 | PLUMBING 1ST REVIEW**DENIED**19100889 | | | | | | 1) SHOW THE WASHER AND DRYER AS BEING ACCESSIBLE WITH A | | | PARALLEL APPROACH CENTERED ON THE FIXTURE FBC-ACC 611.2 | | | AND HEIGHT OF BOTH COMPLYING WITH FBC-ACC 611.4 | | | | | | 2) SHOW CABINET HEIGHT DETAIL AND CLEAR FLOOR SPACE FOR | | | BOTH THE BREAK ROOM SINK AND SINK LOCATED IN THE | | | LAUNDRY ROOM MAX 34?. FBC-ACC 804.3.1, 804.3.2 | | | | | | 3) ARE CUSTOMERS PERMITTED IN THE WORK SPACE TO ACCESS | | | THE DRINKING FOUNTAIN? PLEASE CLARIFY. FBC 107.2.1 | | | | | | 4) PROVIDE BUILDING OCCUPANCY AND OCCUPANT LOAD. FBC | | | 107.3.5 | | | | | | 5) PROVIDE INSTALLATION MANUAL FOR THE TANKLESS WATER | | | HEATER AND GREASE INTERCEPTOR. FBC 107.2.1 | | | | | | 6) PROVIDE TOTAL DEVELOPED LENGTH OF PIPING FOR THE | | | WATER HEATER TO FURTHEST OUTLET. FBC-PLB 607.2 | | | | | | 7) PROVIDE LINT INTERCEPTOR FOR THE WASHING MACHINE. | | | FBC-PLB 1003.6 | | | | | | 8) PROVIDE NOTE RPZ BACKFLOW IF NOT ALREADY ON-SITE | | | WILL BE REQUIRED AND INSTALLATION MUST BE PERFORMED BY | | | A LIC. PLUMBER ONLY WITH SEPARATE PERMIT. SAME OF | | | IRRIGATION SYSTEM ON ITS OWN WATER METER | | | | | | TIM HUNT | | | | | | PLUMBING PLANS EXAMINER | | | | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | | | | 561-248-2703 | | | |
|