2019-11-27 08:09:55PLUMBING 1ST REVIEW**DENIED**19100889
  
 1) SHOW THE WASHER AND DRYER AS BEING ACCESSIBLE WITH A
 PARALLEL APPROACH CENTERED ON THE FIXTURE FBC-ACC 611.2
 AND HEIGHT OF BOTH COMPLYING WITH FBC-ACC 611.4
  
 2) SHOW CABINET HEIGHT DETAIL AND CLEAR FLOOR SPACE FOR
 BOTH THE BREAK ROOM SINK AND SINK LOCATED IN THE
 LAUNDRY ROOM MAX 34?. FBC-ACC 804.3.1, 804.3.2
  
 3) ARE CUSTOMERS PERMITTED IN THE WORK SPACE TO ACCESS
 THE DRINKING FOUNTAIN? PLEASE CLARIFY. FBC 107.2.1
  
 4) PROVIDE BUILDING OCCUPANCY AND OCCUPANT LOAD. FBC
 107.3.5
  
 5) PROVIDE INSTALLATION MANUAL FOR THE TANKLESS WATER
 HEATER AND GREASE INTERCEPTOR. FBC 107.2.1
  
 6) PROVIDE TOTAL DEVELOPED LENGTH OF PIPING FOR THE
 WATER HEATER TO FURTHEST OUTLET. FBC-PLB 607.2
  
 7) PROVIDE LINT INTERCEPTOR FOR THE WASHING MACHINE.
 FBC-PLB 1003.6
  
 8) PROVIDE NOTE RPZ BACKFLOW IF NOT ALREADY ON-SITE
 WILL BE REQUIRED AND INSTALLATION MUST BE PERFORMED BY
 A LIC. PLUMBER ONLY WITH SEPARATE PERMIT. SAME OF
 IRRIGATION SYSTEM ON ITS OWN WATER METER
  
 TIM HUNT
  
 PLUMBING PLANS EXAMINER
  