2019-11-26 15:46:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19100889
 11/26/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2 & M1.1: THE HONEYWELL SENSOR ANALYTICS
 ARE FOR THE SERVICE BAY, HOWEVER NO SERVICE BAY IS
 SHOWN ON THE FLOOR PLAN- SECTION 107.2.1 WPB.
  
 2) M0.2 & M1.1: THE O/A CALCULATIONS IDENITFY SOME OF
 THE SPACES AS BOTH REPAIR AND ENCLOSED PARKING GARAGE.
 PLEASE REVISE THE ANALYTICS AND VENTILATION
 CALCULATIONS TO INDICATE A MINIMUM VENTILATION AIRFLOW
 RATE OF 0.05 CFMS PER SF. SHALL BE MAINTAINED
 CONTINOUSLY- SEE SECTION 404.2 FBC M.
  
 3) M0.2 & M1.1: NO SEQUENCES OF OPERATION ARE PROVIDED
 FOR EF-3, EF-4, AND EF-6. THERE ARE NO SENSORS SHOWN IN
 THESE ROOMS, HOWEVER IT APPEARS VEHICLES WILL BE WORKED
 ON OR STORED IN THESE ROOMS. PLEASE NOTE THAT
 RECIRCULATION OF AIR FROM THE DETAIL AREA VIA THE
 TRANSFERS TO THE CLEAN #1 ROOM MAY BE PROHIBITED
 DEPENDING ON WHAT THE USE OF THE ROOM IS - SEE TABLE
 403.3.1.1 FBC M FOOTNOTE B.
  
 4) M0.2: PLEASE PROVIDE AN AIR BALANCE CALCULATION-
 SECTION 501.4 FBC M.
  
 5) M1.1 PROVIDE FL. PRODUCT APPROVALS OR MIAMI-DADE
 NOA'S FOR THE LOUVERS AND WALL FANS- RULE 9N-3 FAC.
 PLEASE NOTE THAT NOA #16-0209.05 SHOWN ON SHEET M0.5 IS
 EXPIRED.
  
 6) M1.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE AIR
 DRYER AND A PIPING PLAN- SECTION 107.2.1.
  
 7) PROVIDE ENGINEERING FOR INSTALLATION ON THE NEW
 RTU-1- SECTION 301.15 FBC M.
  
 8) THE AC CALCULATIONS ARE INCORRECTLY INDICATING MIAMI
 AS THE PROJECT LOCATION- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  