| Plan Review Notes For Permit 19100889 |
| Permit Number |
19100889 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-21 17:03:55 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PAGE E3.1 FAULLT CURRENT LETTER FROM FPL IS CUT OFF | | | NOT ALL OF IT IS SHOWN | | | | | | 2) PAGE E-3.1 WIRES TO BE TAPPED IN GUTTER ?? NEED TO | | | SHOW SIZE OF CONDUCTORS. | | | | | | 3) PAGE E-3.1 NOTES STATES "OPEN DELTA' ? IS IT OPEN OR | | | CLOSED ? NOT TO MANY OPEN DELTAS EXIST IN THE CITY. |
|