| 2019-12-16 09:23:48 | PLAN REVIEW - ELECTRICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE SERVICE OUTLET AT CU-1 & CU-6. |
| | E3901.12 HVAC OUTLET. |
| | |
| | 2. AVAILABLE FAULT CURRENT FROM FPL TRANSFORMER IS |
| | 30684. FAULT CURRENT USED ON PAGE E-5 FOR AVAILABLE |
| | FAULT CURRENT CALCULATIONS IS 52,205. PLEASE CORRECT. |
| | PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT |
| | AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC |
| | 110.10 & FBC RE E3404.3 |
| | |
| | 3. REMOVE PANEL DP FROM RISER DIAGRAHM. PANEL DP IS TO |
| | BE REMOVED FROM SOW PER RESPONSE LETTER FROM DESIGNER. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PANEL B SHOWS A TOTAL LOAD OF 119 AMPS. OVERCURRENT |
| | PROTECTION FROM MDP IS 100 AMPS. PLEASE CORRECT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |