| Date |
Text |
| 2019-10-22 07:00:47 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | |
| | 1. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET AND SWITCH |
| | CONTROLLED LIGHT FOR SERVICING EACH AHU LOCATED IN AN |
| | ATTIC. FBC MECHANICAL CODE M306.3.1 |
| | |
| | 2. RECEPTACLES IN OUTSIDE GRILL/PATIO AREA MUST BE GFCI |
| | PROTECTED. NEC 210.8A3 |
| | |
| | 3. SERVICE RECEPTACLE WITH GFCI PROTECTION REQUIRED |
| | WITHIN 25FT OF CU OUTSIDE. NEC 210.63 |
| | |
| | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR PANEL P. NEC 225.31, |
| | 225.32 |
| | |
| | 5. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE E3607.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |