| 2019-10-24 11:51:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THESE COMMENTS ARE RELATED TO THE 50 X 60 TENT ONLY: |
| | |
| | 1) THERE ARE NO SITE PLAN. |
| | |
| | PER NFPA 1 |
| | 25.2.1.2 TENTS SHALL BE ERECTED TO COVER NOT MORE THAN |
| | 75 PERCENT |
| | OF THE PREMISES, UNLESS OTHERWISE APPROVED BY THE AHJ. |
| | |
| | 25.2.4 FIRE HAZARDS. |
| | 25.2.4.1 THE FINISHED GROUND LEVEL ENCLOSED BY ANY |
| | TENT, AND THE |
| | FINISHED GROUND LEVEL FOR A REASONABLE DISTANCE, BUT |
| | FOR NOT LESS |
| | THAN 10 FT (3050 MM) OUTSIDE OF SUCH A TENT, SHALL BE |
| | CLEARED OF ALL |
| | FLAMMABLE OR COMBUSTIBLE MATERIAL OR VEGETATION THAT IS |
| | NOT USED |
| | FOR NECESSARY SUPPORT EQUIPMENT. THE CLEARING WORK |
| | SHALL BE |
| | ACCOMPLISHED TO THE SATISFACTION OF THE AHJ PRIOR TO |
| | THE ERECTION |
| | OF SUCH A TENT. THE PREMISES SHALL BE KEPT FREE FROM |
| | SUCH |
| | FLAMMABLE OR COMBUSTIBLE MATERIALS DURING THE PERIOD |
| | FOR WHICH |
| | THE PREMISES ARE USED BY THE PUBLIC. |
| | |
| | PLEASE PROVIDE SITE DIMENSIONS. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF TIE DOWNS. |
| | |
| | PER NFPA 1 |
| | 25.2.3.1 THERE SHALL BE A MINIMUM OF 10 FT (3050 MM) |
| | BETWEEN |
| | STAKE LINES. |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | 3) DOES THIS TENT HAVE SIDES AND EXIT DOORS? |
| | |
| | PLEASE PROVIDE DETAILS AND DIMENSIONS. |
| | |
| | |
| | |
| | 4) DOES THIS TENT HAVE LLUMINATED EXIT SIGNS AS IT WILL |
| | OCCUPIED DURING THE EVENING? |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |