2019-10-31 07:26:2510/31/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. HEATED SWIMMING POOLS AND INGROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC-
 ENERGY- SEC. R 403.10.3.
 2. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.3.
 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  