Plan Review Notes
Plan Review Notes For Permit 19100815
Permit Number 19100815
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-10-23 11:33:051. UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY REVIEW
 COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE (2015
 EDITION WITH FLORIDA AMENDMENTS.)
  
 2. ALL WORK SHOULD ALSO REFERENCE COMPLIANCE TO NFPA
 110 ( STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
 ) AND 37 (STANDARD FOR THE INSTALLATION AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES)
  
 3. PER NFPA 110:7.9.1.1 ALL FUEL TANKS AND SYSTEMS
 SHALL BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH
 NFPA 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE; NFPA
 37, STANDARD FOR THE INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES; NFPA 54, NATIONAL
 FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS
 CODE.
  
 4.PER NFPA 110:4 THE GENERATOR SHALL BE OF A CERTAIN
 CLASS/TYPE/LEVEL. PLEASE PROVIDE CLARIFICATION AS TO
 THE CLASS/TYPE/LEVEL.
  
 5. PAGE E2.1.19 SHOWS FUEL CALCULATIONS, HOWEVER THERE
 IS NO PLAN INDICATION THE MEANS AND QUANTITY OF FUEL
 STORAGE.
  
 6. ALL WORK SHALL BE SUBJECT TO FIELD INSPECTION.
  
  