| 2019-10-31 13:32:11 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE TWO SETS OF A FLOOR PLAN THAT INDICATES THE | | | LOCATION OF THE PROPOSED WALL AND DOOR. FBC CITY | | | AMENDMENTS 107.2 | | | | | | 2) SHOW ON THE PLANS THAT THE NEW DOOR WILL COMPLY WITH | | | FBC ACCESSIBILITY SECTION 404.2.4.1 MANEUVERING | | | CLEARANCES THAT REQUIRE A MINIMUM OF 18" CLEARANCE ON | | | THE PULL SIDE OF THE DOOR. | | | | | | 3) INDICATE THE EXIT SIGN LOCATIONS ON THE PLANS. FBC | | | 1013.1 | | | | | | 4) FBC 602.2 TYPE I AND II CONSTRUCTION REQUIRES | | | INTERIOR WALLS TO BE CONSTRUCTED OF NONCOMBUSTIBLE | | | MATERIALS EXCEPT AS PERMITTED IN SECTION 603. THIS | | | BUILDING IS TYPE I-B. SPECIFY THE MATERIALS THAT WILL | | | BE USED TO CONSTRUCT THE WALL. | | | | | | 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | |
|