| 2020-01-02 14:48:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE CLEAR FLOOR SPACES FOR |
| | APPLICABLE BATHROOMS TO SHOW COMPLIANCE WITH THE FAIR |
| | HOUSING ACT. COMPLIED |
| | |
| | 2. THE SANITARY ISOMETRIC FOR THE WASHER/SHOWER/WATER |
| | CLOSET STACKS IS NON-COMPLIANT. PER WPB FBC 107.2.1, |
| | SHOW HOW THE FIXTURES ARE BEING VENTED IN ACCORDANCE |
| | WITH THE REQUIREMENTS OF FBC PL CHAPTER 9. |
| | DID NOT COMPLY: A SANITARY ISOMETRIC IS STILL REQUIRED |
| | TO SHOW CAPPED TUB DRAIN, CONNECTIONS OF THE TWO |
| | RECONFIGURED LAVATORIES AND CAPPING OF RELOCATED |
| | LAVATORY WHICH WAS ADJACENT TO THE SHOWER. SHOW VENTING |
| | AND DRAINAGE OF ALL FIXTURES AND CONNECTIONS TO STACKS. |
| | |
| | 3. ANY NEW FLOOR PENETRATIONS SHALL MEET THE |
| | REQUIREMENTS OF FBC CHAPTER 7. |
| | DID NOT COMPLY |
| | THE WATER CLOSET FLOOR PENETRATION WILL HAVE TO BE |
| | RELOCATED IN ORDER TO PHYSICALLY ACCOMMODATE THE |
| | RECONFIGURATION OF THE FIXTURE. |
| | ADDITIONALLY THE DELETED TUB PENETRATION OPENING WILL |
| | HAVE TO BE SAFED |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19100754 801 S OLIVE AVE 1105 |
| | |
| | |