| 2019-10-24 07:14:58 | 10/24/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1- PLEASE SUBMIT A SPERATE PLUMBING PERMIT APPLICATION |
| | FOR THE ROOF DRAINS, GREASE TRAP, ALL INTERIOR/ |
| | EXTERIOR PLUMBING. PLUMBING SHALL BE DONE BY A LICENSED |
| | PLUMBING CONTRACTOR. |
| | |
| | 2- SIGNATURE OF AN ARCHITECT-ENGINEER IS REQUIRED (OR |
| | SEAL, OR TITLE BLOCK, OR ALL THREE) ARE NOT IN |
| | ACCORDANCE WITH FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.001, FLORIDA STATUTE 471. |
| | |
| | 3- PLEASE SHOW DIMENSIONS ON THE PLAN INDICATING THE |
| | BUILDINGS ACTUAL ROOF SIZE |
| | |
| | 4- THE ADDRESS ON THE SUBMITTED PLANS IS DIFFERENT THAN |
| | THE ADDRESS LISTED ON THE PERMIT APPLICATION |
| | |
| | 5- INDICATE ON THE PLAN ALL ROOF DRAINS TO BE |
| | INSTALLED, PLAN PAGE E 1.2 SHOWS SOME ADDITIONAL ROOF |
| | DRAINS NOT SHOWN ON C-1. |
| | |
| | 6- PROVIDE 2-COPIES OF SPECIFICATIONS FOR THE TYPE OF |
| | ROOF DRAINS THAT ARE TO BE INSTALLED |
| | |
| | 7- PROVIDE AN ISOMETRIC SHOWING THE ENTIRE ROOF |
| | DRAINAGE SYSTEM |
| | |
| | 8- FLOOR DRAIN CONNECTED TO GREASE TRAP IN DUMPSTER |
| | AREA SHALL NOT RECIEVE ANY RAIN WATER, HOW WILL THE |
| | DUMPSTER PAD BE ELEVATED ABOVE THE SORROUNDING AREA |
| | OUTSIDE OF THE DUMPSTER ? |
| | |
| | |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLANS EXAMINER |
| | AVAILABLE BY APPOINTMENT ONLY |
| | [email protected] |