2019-10-30 11:16:171ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SAMPLING PORT SHALL NOT BE A SANITARY CROSS A
 SUMP IS PROHIBITED IT SHALL BE A 4" TWO WAY CLEAN OUT
 OR A MANUFACTURE SAMPLING PORT. PER WPB UTILITIES
 DEPARTMENT STANDARD DETAILGS-7 AND 7.1
  
 2. THE GREASE INTERCEPTOR SHALL NOT CONNECT TOGETHER
 BEFORE CONNECTING TO SANITARY THEY SHALL CONNECT TO
 SANITARY SEPARATELY THEY ARE SIZED SEPARATELY FOR EACH
 OCCUPANCY. PER FBC PL 1003.2 - 1003.3.1
  
 3. PROVIDE SIZING CALCULATION FOR REVISED ROOF DRAINS.
 PER WPB AMEND TO FBC 107.2.1.
  
 4. PROVIDE PLUMBING DRAWINGS FOR REVISIONS PER WPB
 AMEND TO FBC 107.2.1.
  
  
 5. ADDRESS ON PLAN DOES NOT MATCH ADDRESS ON PERMIT
 PLAN IS 327 HIBISCUS PERMIT IS 518
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  