| 2019-10-30 11:16:17 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE SAMPLING PORT SHALL NOT BE A SANITARY CROSS A |
| | SUMP IS PROHIBITED IT SHALL BE A 4" TWO WAY CLEAN OUT |
| | OR A MANUFACTURE SAMPLING PORT. PER WPB UTILITIES |
| | DEPARTMENT STANDARD DETAILGS-7 AND 7.1 |
| | |
| | 2. THE GREASE INTERCEPTOR SHALL NOT CONNECT TOGETHER |
| | BEFORE CONNECTING TO SANITARY THEY SHALL CONNECT TO |
| | SANITARY SEPARATELY THEY ARE SIZED SEPARATELY FOR EACH |
| | OCCUPANCY. PER FBC PL 1003.2 - 1003.3.1 |
| | |
| | 3. PROVIDE SIZING CALCULATION FOR REVISED ROOF DRAINS. |
| | PER WPB AMEND TO FBC 107.2.1. |
| | |
| | 4. PROVIDE PLUMBING DRAWINGS FOR REVISIONS PER WPB |
| | AMEND TO FBC 107.2.1. |
| | |
| | |
| | 5. ADDRESS ON PLAN DOES NOT MATCH ADDRESS ON PERMIT |
| | PLAN IS 327 HIBISCUS PERMIT IS 518 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |