| Plan Review Notes For Permit 19100703 |
| Permit Number |
19100703 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-12-04 17:56:02 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE DRAWINGS IN ELECTRONIC FORMAT FROM THE DELEGATE | | | ENGINEER, CHRISTOPHER STANTON, FOR THE STOREFRONT | | | ASSEMBLIES DO NOT HIS DIGITAL SIGNATURE AS REQUIRED BY | | | FS 471 & FAC 61G-15 | | | | | | 2) THE STOREFRONT DRAWINGS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED FOR COMPATIBILITY WITH THE DESIGN OF THE | | | BUILDING IN WRITING BY THE DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE PER FBC 107.3.4. | | | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL | | | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE | | | ENGINEER OF RECORD FOR REVIEW. | | | | | | 3) THE PRODUCT APPROVALS FOR THE STOREFRONTS AND THE | | | EXTERIOR DOORS DO NOT HAVE THE ENGINEER'S REVIEW STAMP | | | ON THEM. 107.3.4 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY FAC 61G20 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | |
|