2019-11-14 11:43:52RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS.
  
 B) SINGLE HUNG WINDOW AS SHOWN ON PLANS.
  
 C) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 3- NEED TO PROVIDE COMPLETE FRAMING DETAILS ANS
 SPECIFICATIONS FOR THE NEW EXTERIOR DOOR AND WINDOW.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC.
 R301.2.1 FBC-RESIDENTIAL.
  
 4- NEED TO PROVIDE ATTACHMENT OF THE NEW WOOD FRAMED
 WALL TO EXISTING STEEL COLUMN. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 5- NEED TO PROVIDE ATTACHMENT OF THE NEW WOOD FRAMED
 WALL TO EXISTING CONCRETE BLOCK WALL. COLUMN. SEC.
 R301.2.1 FBC-RESIDENTIAL.
  
 6- NEED TO PROVIDE ATTACHMENT OF THE NEW WOOD FRAMED
 WALL TO EXISTING BEAM SEC. R301.2.1 FBC-RESIDENTIAL.
  
 7- THIS IS A CHANGE OF USE FROM CARPORT TO ENCLOSED
 SPACE. TYPICALLY, CARPORTS ARE BUILT WITHOUT A FLOOR
 VAPOR BARRIER. ENGINEER OF RECORD TO PROVIDE
 SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER AS
 REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL OR PROVIDE
 PROOF THAT THERE IS AN EXISTING VAPOR BARRIER.
  
 8- NEED TO PROVIDE ATTACHMENT OF THE NEW WALL
 SHEATHING. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 9- NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL ON THE
 WOOD FRAMED WALL.
  
 10- NEED TO SPECIFY MIN. 7/8" STUCCO THICKNESS FOR
 EXTERIOR APPLICATIONS AS REQUIRED BY SEC. R702.2.2 AND
 TABLE R702.1(1) FBC-RESIDENTIAL.
  
 11- A) ENGINEER TO REVISE THE BUILDING EXPOSURE.
 ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE C NOT B. REVISE AS
 REQUIRED OR PROVIDE CALCULATIONS AND SPECIFY THE
 BUILDING EXPOSURE FOR EACH WIND DIRECTION.
  
 B) REVISE THE WINDOWS AND DOORS DESIGN PRESSURES.
 COORDINATE WITH REVISED BUILDING EXPOSURE. AND,
 ENGINEER TO CLARIFY IF THE DESIGN PRESSURES ARE GIVEN
 IN ULTIMATED DESIGN PRESSURES OR NOMINAL DESIGN
 PRESSRUES. SEC. R301.2.1.3 FBC-RESIDENTIAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved