| 2019-10-21 08:58:20 | GAS REVIEW REVISION #1**DENIED** |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-RES |
| | SEC. G2413.4.1, G2413.4.2. PROVIDE TOTAL DISTANCE OF |
| | COPPER TUBING. NO DISTANCE IS SHOWN ON PLAN OR ON |
| | SIZING CHART. FBC 107.3.5 |
| | |
| | |
| | 2. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 3. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4 |
| | |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. |
| | |
| | 5. YOUR TIE DOWN PLAN DOES NOT SHOW MEETING THE FBC FOR |
| | UP LIFT AS IT ONLY SHOWS THE CABLE WRAPPING AROUND THE |
| | TANK WITH NO EYE FOR THE CABLE TO GO THOUGH. FBC 107.2 |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |