| 2019-10-16 12:05:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THE SUBMITTED FLOOR PLAN DOES NOT HAVE ANY | | | DIMENSIONS TO VERIFY COVERAGE AREA NOR DISTANCE BETWEEN | | | HEADS AND OTHER EXISTING HEADS THAT MAY BE IN THE AREA. | | | | | | PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE. | | | | | | | | | | | | 2) A SITE REVIEW WAS DONE AND IT WAS NOTED THAT AN | | | ADDITIONAL HEAD WAS NEEDED. IT IS NOT SHOWN HERE. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY. | | | | | | | | | | | | 3) SPECIFICATION SHEETS ARE PROVIDED; HOWEVER, THE HEAD | | | INDICATED IS FOR A 8.0K FACTOR. | | | | | | THERE ARE NO HYDRAULIC CALCULATIONS PROVIDED TO VERIFY | | | THAT THESE HEADS WILL WORK IN THIS PRE=EXISTING | | | CLACULATED DESIGN. | | | | | | PLEASE REVIEW AND PROVIDE. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|