| 2020-03-19 09:15:58 | PLAN REVIEW - PLUMBING |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. DRAIN SIZE NOT SHOWN FOR 3RD FLOOR TO 2ND FLOOR |
| | BATHROOM GROUP. |
| | P3005.4DRAIN PIPE SIZING. |
| | DRAIN PIPES SHALL BE SIZED ACCORDING TO DRAINAGE |
| | FIXTURE UNIT (D.F.U.) LOADS. THE SIZE OF THE DRAINAGE |
| | PIPING SHALL NOT BE REDUCED IN SIZE IN THE DIRECTION OF |
| | FLOW. THE FOLLOWING GENERAL PROCEDURE IS PERMITTED TO |
| | BE USED: |
| | |
| | 2. VENT SIZE FROM 2ND TO 3RD FLOOR NOT SHOWN ON ISO. |
| | P3102.3SIZE. |
| | THE REQUIRED VENT SHALL BE SIZED IN ACCORDANCE WITH |
| | SECTION P3113.1 BASED ON THE REQUIRED SIZE OF THE |
| | BUILDING DRAIN. |
| | |
| | 3. 3RD FLOOR VTR NOT SIZED ON ISO. |
| | P3102.3SIZE. |
| | THE REQUIRED VENT SHALL BE SIZED IN ACCORDANCE WITH |
| | SECTION P3113.1 BASED ON THE REQUIRED SIZE OF THE |
| | BUILDING DRAIN. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |