Plan Review Notes
Plan Review Notes For Permit 19100651
Permit Number 19100651
Review Stop P
Sequence Number 2
Notes
Date Text
2020-03-19 09:15:58PLAN REVIEW - PLUMBING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DRAIN SIZE NOT SHOWN FOR 3RD FLOOR TO 2ND FLOOR
 BATHROOM GROUP.
 P3005.4DRAIN PIPE SIZING.
 DRAIN PIPES SHALL BE SIZED ACCORDING TO DRAINAGE
 FIXTURE UNIT (D.F.U.) LOADS. THE SIZE OF THE DRAINAGE
 PIPING SHALL NOT BE REDUCED IN SIZE IN THE DIRECTION OF
 FLOW. THE FOLLOWING GENERAL PROCEDURE IS PERMITTED TO
 BE USED:
  
 2. VENT SIZE FROM 2ND TO 3RD FLOOR NOT SHOWN ON ISO.
 P3102.3SIZE.
 THE REQUIRED VENT SHALL BE SIZED IN ACCORDANCE WITH
 SECTION P3113.1 BASED ON THE REQUIRED SIZE OF THE
 BUILDING DRAIN.
  
 3. 3RD FLOOR VTR NOT SIZED ON ISO.
 P3102.3SIZE.
 THE REQUIRED VENT SHALL BE SIZED IN ACCORDANCE WITH
 SECTION P3113.1 BASED ON THE REQUIRED SIZE OF THE
 BUILDING DRAIN.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved