2020-03-16 09:25:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET 024_EL, THE 24 26 16 PANEL SCHEDULE LOCATED
 NEXT TO THE LOAD CALCULATION STATES THAT THERE WILL BE
 100 AMP BREAKERS FEEDING THE THREE SUB-PANELS. THE
 PANEL SCHEDULE FOR THIS PANEL LOCATED AT THE TOP OF THE
 PAGE STATES THAT THEY ARE FED WITH 20 AMP CIRCUITS.
 CORRECT DISCREPANCY. WPB FBC 107.2.1
 2. SHEET 024_EL, THE 24 26 16 PANEL SCHEDULE LOCATED
 NEXT TO THE LOAD CALCULATION STATES THAT THE WIRE SIZE
 FEEDING THE THREE SUB-PANELS WILL BE # 4. THIS WIRE
 SIZE IS NOT RATED FOR 100 AMPS. PROVIDE CORRECTION.
 WIRE SIZES FROM NEC 310.15(B)(7), OR FBC RE E3603.1,
 CAN ONLY BE USED WHEN THE SERVICE CONDUCTOR SUPPLIES
 100% OF THE LOAD. SINCE THIS IS NOT THE CASE, PROVIDE
 CORRECTED WIRE SIZE FROM METER CAN TO PANELS. NEC
 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1
 3. SHEET 024_EL, THE 24 26 16 PANEL SCHEDULE LOCATED
 NEXT TO THE LOAD CALCULATION SHOWS A GROUNDING
 ELECTRODE CONDUCTOR TO EACH SUB-PANEL. THE GROUNDING
 ELECTRODE CONDUCTOR IS ONLY CONNECTED AT THE MAIN. AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED TO CODE, IS
 REQUIRED TO BE INSTALLED WITH ALL FEEDERS TO
 SUB-PANELS. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6, 3607.3.1
 4. PLAN IS NOT CLEAR AS TO THE OVER-CURRENT PROTECTION
 OF FEEDERS TO THE SUB-PANELS. THESE CIRCUITS NEED TO BE
 PROTECTED AT THE SOURCE, THE MAIN DISTRIBUTION PANEL.
 IF THE INTENT IS TO TAP OFF THE MAIN 300 WITH THESE
 FEEDERS, THESE TAPS WOULD NEED T COMPLY WITH THE TAP
 RULES PER NEC 240.21. THE PANEL SCHEDULES STATES THEY
 ARE MAIN LUG ONLY, BUT ALSO STATE THERE IS A 100 AMP
 MAIN. WHICH IS IT? PROVIDE CLARIFICATION AND/OR
 CORRECTIONS. WPB FBC 107.2.1; NEC 240.4, 240.21
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 6. PROVIDE LOAD CALCULATION FOR EACH SUB-PANEL (P.1,
 P.2, P.3). BASED ON THE CONNECTED LOAD SHOWN, EACH OF
 THESE PANELS IS OVERLOADED. PROVIDE CORRECTION. NEC
 215.2, 220, 408.30; FBC RE E3602.2
 7. CIRCUIT #24 FROM P.1 IS SHOWN FEEDING LIGHTS AND
 RECEPTACLES IN MORE THAN ONE BATHROOM. THIS IS NOT
 PERMITTED PER CODE. AN INDIVIDUAL 20 AMP CIRCUIT IS
 ALLOWED TO FEED LIGNTS AND RECEPTACLES IN ONE BATHROOM
 IF IT DOES NOT EXTEND TO OTHER BATHROOMS. OR, A
 SEPARATE CIRCUIT CAN BE USED FOR LIGHTING, AND THE
 RECEPTACLE CIRCUIT CAN FEED OTHER BATHROOMS. AS SHOWN
 ON PLAN, THE CIRCUITRY IS NOT CODE COMPLIANT. PROVIDE
 CORRECTION. NEC 210.11(C)(3); FBC RE E3703.4
 8. CIRCUIT #17 FROM P.2 IS SHOWN FEEDING LIGHTS AND
 RECEPTACLES IN MORE THAN ONE BATHROOM. THIS IS NOT
 PERMITTED PER CODE. AN INDIVIDUAL 20 AMP CIRCUIT IS
 ALLOWED TO FEED LIGNTS AND RECEPTACLES IN ONE BATHROOM
 IF IT DOES NOT EXTEND TO OTHER BATHROOMS. OR, A
 SEPARATE CIRCUIT CAN BE USED FOR LIGHTING, AND THE
 RECEPTACLE CIRCUIT CAN FEED OTHER BATHROOMS. AS SHOWN
 ON PLAN, THE CIRCUITRY IS NOT CODE COMPLIANT. PROVIDE
 CORRECTION. NEC 210.11(C)(3); FBC RE E3703.4
 9. CIRCUIT #17 FROM P.3 IS SHOWN FEEDING LIGHTS AND
 RECEPTACLES IN MORE THAN ONE BATHROOM. THIS IS NOT
 PERMITTED PER CODE. AN INDIVIDUAL 20 AMP CIRCUIT IS
 ALLOWED TO FEED LIGNTS AND RECEPTACLES IN ONE BATHROOM
 IF IT DOES NOT EXTEND TO OTHER BATHROOMS. OR, A
 SEPARATE CIRCUIT CAN BE USED FOR LIGHTING, AND THE
 RECEPTACLE CIRCUIT CAN FEED OTHER BATHROOMS. AS SHOWN
 ON PLAN, THE CIRCUITRY IS NOT CODE COMPLIANT. PROVIDE
 CORRECTION. NEC 210.11(C)(3); FBC RE E3703.4
 10. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. SHOW LOCATION OF UNITS ON PLAN. WPB
 FBC 107.2.1; NEC 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER