| 2020-02-27 08:20:49 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19100568 |
| | 2/27/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENTS REMAINING FROM THE 1ST REVIEW ARE LISTED |
| | BELOW- PLEASE RESUBMIT CORRECTED PLANS AND THE |
| | REQUESTED CALCULATIONS. |
| | |
| | 1) THE NEW ENERGY COMPLIANCE FORM R405-2017 LISTS THE |
| | NEW A C SYSTEM AS A 24,000 BTUH (2-TON) 14 SEER SYSTEM, |
| | HOWEVER THE EQUIPMENT SCHEDULED ON SHEET M-1 INDICATES |
| | A 30,000 BTUH (2.5 TON) 13 SEER SYSTEM. PLEAAE MATCH |
| | THE SYSTEMS ONE WAY OR THE OTHER. |
| | |
| | 2) 3RD REQUEST: PROVIDE MANUAL J COOLING AND HEATING |
| | CALCULATIONS FOR THE NEW AC SYSTEM- SECTION R403.6.1 |
| | FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |