| 2020-03-06 15:07:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. AFCI PROTECTION DETAILED IN NEW ELECTRIC NOTE IS NOT |
| | CODE COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY |
| | 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| | INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| | PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND |
| | RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12; FBC |
| | RE E3902; FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS |
| | APPLICABLE. (NOT CORRECTED.)(3RD REVIEW: NOTE IS |
| | CORRECTED IN ONE LOCATION, BUT NOT THE OTHER. CORRECT |
| | DISCREPANCY.) |
| | 2. UNDER NEW ELECTRIC NOTE AND NOTE 14, THESE NOTES |
| | STATE THAT RECEPTACLES SHALL BE TAMPER RESISTANT PER |
| | NEC 406.11. THIS CODE SECTION DOES NOT APPLY TO TAMPER |
| | RESISTANT RECEPTACLES. PROVIDE CORRECTION. NEC 406.12; |
| | FBC RE E4002.14 (NOT CORRECTED.)(3RD REVIEW: NOTE IS |
| | CORRECTED IN ONE LOCATION, BUT NOT THE OTHER. CORRECT |
| | DISCREPANCY.) |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 (NOT PROVIDED.)(3RD REVIEW: STILL NOT |
| | PROVIDED.) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. RISER DIAGRAM SHOWS A FEED FROM THE METER TO THE |
| | INTERIOR PANEL WHICH IS LOCATED IN THE HALLWAY. |
| | CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR |
| | DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE |
| | IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE |
| | OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB. |
| | IF THERE IS A DISCONNECT AT THE METER, THE CONDUIT TO |
| | THE INTERIOR PANEL SHALL INCLUDE AN EQUIPMENT GROUNDING |
| | CONDUCTOR. PROVIDE CORRECTIONS. NEC 230.70, 250.6, |
| | 250.118; FBC RE E3601.6 (NOT CORRECTED.)(3RD REVIEW: |
| | STILL NOT CORRECTED.) |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT. |
| | NEC 220; FBC RE E3602.2 (NOT PROVIDED. THERE ARE |
| | SEVERAL PROBLEMS WITH CALCULATION. ALSO, WHAT IS THE |
| | SIZE OF THE TANKLESS WATER HEATER BEING USED. PANEL |
| | SCHEDULE SAYS IT IS 3500 VA, BUT THIS IS NOT ONE OF THE |
| | SIZES SHOWN ON CUT SHEET PROVIDED.)(3RD REVIEW: STILL |
| | NOT CORRECTED. CALCULATION SHOULD BE OF THE TYPE FOR A |
| | DWELLING UNIT, AS SPEICIFED IN FBC RE 3602.2) |
| | 12. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |