| 2021-06-24 15:44:41 | RESIDENTIAL (R3) ADDITION/ALTERATION, SIXTH BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | PERMIT # 19100548 |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5 |
| | FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | ENERGY CALCULATIONS SUBMITTED: |
| | |
| | NOTE: |
| | FORM R405-2020 SUBMITTED NOW IS THE WRONG FORM. THIS |
| | PROJECT IS REVIEWED UNDER THE 2017 CODE. PROVIDE |
| | CORRECT FORM R405-2017 AS DONE ON PREVIOUS SUBMITTAL. |
| | |
| | REPEAT COMMENT (THREE TIMES): |
| | A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION. |
| | |
| | B) OK. |
| | C) OK. |
| | |
| | REPEAT COMMENT. |
| | D) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 |
| | TO MATCH PLANS. THIS IS FOR ENTIRE FIRST FLOOR. SEE |
| | PLANS/ELEVATIONS AND REVISE AS REQUIRED. CHECK WINDOWS |
| | OVERHANG AND SEPARATION ALSO. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E)OK. |
| | |
| | REPEAT COMMENT. |
| | F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD SUBMITTED SEC. R405.4.3 FBC- |
| | ENERGY CONSERVATION. |
| | |
| | NEW COMMENTS: |
| | G) ITEM #3 IS INCORRECT. COORDINATE WITH ITEM 1(G) |
| | ABOVE AND REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | 2- OK. |
| | 3- OK |
| | 4- OK. |
| | 5- OK. |
| | 6- OK |
| | |
| | ORIGINAL COMMENT. |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | |
| | A)EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. |
| | DESIGN PRESSURES (+/- 35) SHOWN ON DOOR FLORIDA PRODUCT |
| | APPROVAL FL11861-R8 SUBMITTED DON'T MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| | NEED TO PROVIDE PRODUCT APPROVAL FOR DOOR THAT MEETS |
| | THE CALCULATED DESIGN PRESSURES. NOTE: NEED TO |
| | COORDINATE WITH REVISED DESIGN PRESSURES ON ITEM #5 |
| | ABOVE. |
| | |
| | B)OK |
| | |
| | C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT |
| | APPROVALS DON'T HAVE IMPACT GLAZING. |
| | PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 |
| | FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING |
| | |
| | NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE |
| | INSTALLATION SCHEDULE AS REQUIRED BY CITY |
| | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT |
| | PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY |
| | SAMPLE |
| | |
| | REPEAT COMMENT: |
| | D) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 9- FLOOR PLANS AND ELEVATIONS STATE THAT THE NEW STAIRS |
| | TO THE SECOND FLOOR ARE TO BE DONE BY OTHERS. PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS FOR THIS STAIRWAY |
| | OR CLARIFY IF SUBMITTING THIS INFORMATION UNDER A |
| | SEPARATE PERMIT. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | DESIGNER OF RECORD TO PROVIDE COMPLETE |
| | DETAILS/SPECIFICATIONS OR INDICATE IF THIS WORK IS |
| | UNDER A SEPARATE PERMIT. |
| | |
| | 10- OK. |
| | |
| | 11- OK. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |