| 2021-03-12 12:05:42 | RESIDENTIAL (R3) ADDITION/ALTERATION, FIFTH BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | PERMIT # 19100548 |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5 |
| | FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | ENERGY CALCULATIONS SUBMITTED: |
| | |
| | REPEAT COMMENT. |
| | A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION. |
| | |
| | REPEAT COMMENT. |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC- |
| | ENERGY CONSERVATION. |
| | |
| | REPEAT COMMENT. |
| | C) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4 IS |
| | INCORRECT. IT DOESN'T MATCH PLANS. SEE PLANS AND REVISE |
| | AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | REPEAT COMMENT. |
| | D) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 |
| | TO MATCH PLANS. THIS IS FOR ENTIRE FIRST FLOOR. SEE |
| | PLANS/ELEVATIONS AND REVISE AS REQUIRED. CHECK WINDOWS |
| | OVERHANG AND SEPARATION ALSO. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 3 OF 4 |
| | DOESN'T MATCH PLANS/ELEVATIONS. PLANS SHOW FLAT ROOF NO |
| | HIP. SEE PLANS AND REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD SUBMITTED SEC. R405.4.3 FBC- |
| | ENERGY CONSERVATION. |
| | |
| | 2- OK. |
| | 3- OK |
| | 4- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1 |
| | ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2) |
| | FBC-RESIDENTIAL AS SPECIFIED ON PLANS. SEE TABLE |
| | R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED. USE |
| | THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA AS |
| | REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR PROVIDE |
| | CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED ON THE |
| | LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHT AND |
| | BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | REVISE DESIGN PRESSURES AGAIN. PRESSURES GIVEN ARE |
| | TAKING FROM TABLE R301.2(2) FBC-RESIDENTIAL. THIS |
| | BUILDING IS IN EXPOSURE "C". NEED TO MULTIPLE PRESSURES |
| | BY COEFFICIENT SHOWN ON TABLE R301.2(3) FBC-RESIDENTIAL |
| | BASED ON THE HEIGHT OF THE BUILDING. REVISE AS |
| | REQUIRED. NOTE: THIS IS A TWO STORY BUILDING. |
| | |
| | 6- OK |
| | |
| | ORIGINAL COMMENT. |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL) |
| | |
| | A)EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | RESPONSE: |
| | DESIGN PRESSURES (+/- 35) SHOWN ON DOOR FLORIDA PRODUCT |
| | APPROVAL FL11861-R8 SUBMITTED DON'T MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| | NEED TO PROVIDE PRODUCT APPROVAL FOR DOOR THAT MEETS |
| | THE CALCULATED DESIGN PRESSURES. NOTE: NEED TO |
| | COORDINATE WITH REVISED DESIGN PRESSURES ON ITEM #5 |
| | ABOVE. |
| | |
| | B)SINGLE HUNG WINDOWS. OK |
| | |
| | C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT |
| | APPROVALS DON'T HAVE IMPACT GLAZING. |
| | PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 |
| | FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING |
| | |
| | RESPONSE: |
| | SWING DOOR PRODUCT APPROVAL SUBMITTED DON'T HAVE IMPACT |
| | GLAZING. COORDINATE WITH ITEM # 7.A) ABOVE. |
| | |
| | NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE |
| | INSTALLATION SCHEDULE AS REQUIRED BY CITY |
| | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT |
| | PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY |
| | SAMPLE |
| | |
| | D) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED AT ALL. CONTRACTOR DIDN'T |
| | EVEN SPECIFIED IF SUBMITTING LATER AS A DEFERRED |
| | SUBMITTAL. |
| | |
| | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9- FLOOR PLANS AND ELEVATIONS STATE THAT THE NEW STAIRS |
| | TO THE SECOND FLOOR ARE TO BE DONE BY OTHERS. PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS FOR THIS STAIRWAY |
| | OR CLARIFY IF SUBMITTING THIS INFORMATION UNDER A |
| | SEPARATE PERMIT. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 10- ALL DRAWINGS SUBMITTED ARE NOT SIGNED AND SEALED BY |
| | THE ARCHITECT OF RECORD. ARCHITECT TO SIGN AND SEAL |
| | DRAWING AS REQUIRED BY 61G1-16.001FAC AND CHAPTER 481 |
| | F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE |
| | OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL |
| | AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL |
| | FOR RECORDS RETENTION. |
| | |
| | 11- ARCHITECT TO REVISE TYPICALLY WALL SECTION ON SHEET |
| | 3.1. |
| | SCREEN VENTS SPACED AT 6'-0" O.C. DON'T PROVIDE CROSS |
| | VENTILATION AS REQUIRED BY SEC. R806 FBC-RESIDENTIAL. |
| | THIS IS A FLAT ROOF WITH SOLID 2X12 ROOF JOISTS. |
| | TYPICALLY, A CONTINUOUS VENT IS INSTALLED IN THIS TYPE |
| | OF ROOFS. REVISE AS REQUIRED. SPECIFY VENT TYPE AND |
| | SIZE THAT WILL PROVIDE REQUIRED CROSS VENTILATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |