| 2019-10-22 13:47:15 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE DETAILED SCOPE OF PLUMBING WORK BEING DONE |
| | PLAN IS UNCLEAR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. BY INCLUDING THE SANITARY ISOMETRIC DRAWING IT |
| | APPEARS THAT THE SANITARY PIPING SYSTEM IS BEING |
| | REPLACED IF YOU ONLY MOVING THE TOILET A ISOMETRIC |
| | DRAWING IS NOT REQUIRED PLEASE CORRECT THE FOLLOWING |
| | CODE VIOLATIONS ON THE ISOMETRIC. |
| | A)THE KITCHEN BRANCH DRAIN CAN NOT CONNECT TO BATHROOM |
| | GROUP SHALL CONNECT DOWN STREAM. PER FBC RES P3108.1 |
| | B)SHOWER SHALL CONNECT TO BATHROOM GROUP AND BE VENTED |
| | BY LAVATORY OR BE INDIVIDUALLY VENTED.PER FBC RES |
| | P3108.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |