| Date |
Text |
| 2019-10-31 14:20:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PERMIT APPLICATION STATES THIS IS A FULL RENOVATION. |
| | THERE ARE NO ELECTRICAL PLANS FOR THE SECOND FLOOR. |
| | PROVIDE FULL SET OF PLANS FOR REVIEW. WPB FBC 107.2.1 |
| | 2. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| | 801.2, OR 901.2 AS APPLICABLE. |
| | 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| | BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| | FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| | R314.3(4), NFPA 72:29.8.3.4 |
| | 4. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |