| 2020-05-31 08:24:31 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19100523 |
| | ADD: 311 N. SAPODILLA AVE. (DUMPSTER ENCLOSURE) |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL:??? CONTACT: PIERRE KETLENE |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. MAY 31/2020 |
| | ACTION: DENIED |
| | |
| | 1) THIS PROJECT BEING PERMITTED IS FOR THE BUILDING OF |
| | A DUMPSTER ENCLOSURE. THERE ARE SHEETS THAT WERE |
| | SUBMITTED THAT HAVE NO BEARING ON THE DUMPSTER |
| | ENCLOSURE. |
| | SHEET 319A THE PROPOSED FLOOR PLAN. |
| | SHEET 401S THIS DESIGN CRITERIA AS LISTED IS FOR THE |
| | MAIN BUILDING THAT WOULD BE REMODELED, DESIGN IS FOR AN |
| | ENCLOSED BUILDING, IMPORTANCE FACTOR, AND ROOF |
| | PRESSURES THAT ARE GIVEN ARE ALL FOR AN ENCLOSED |
| | BUILDING. NOTHING IS FOR THE DUMPSTER ENCLOSURE. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) SHEET 333A DETAIL # 6 SHOWS DETAIL B, C, & D |
| | ELEVATION WITH A 6 INCH BLOCK WALL AND A 8 INCH |
| | CONCRETE CAP WITH AN 2 INCH OFFSET TO THE EXTERIOR |
| | SIDE. SHEET 406S4.0 DETAIL # 1 SECTION AT TRASH |
| | ENCLOSURE SHOWS THE WALL WITH AN 8 INCH CONCRETE CAP |
| | AND 8 INCH BLOCK WALL. SHEET 403S3.0 ALSO STATES THE |
| | BLOCK WALL IS TO BE 8 INCH CONCRETE BLOCK? |
| | DISCREPANCY IN PLANS, PLEASE CORRECT THE DISCREPANCY. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET 406S4.0 DETAIL 1 ALSO SHOWS THE FOUNDATION BUT |
| | NO SIZE NOR STEEL REINFORMENT INFORMATION IS GIVEN NOR |
| | A IDENTIFICATION MARKER TO NAME THE FOOTER. SHEET |
| | 403S3.0 DOES HAVE FOOTER SIZE AND STEEL SIZING AND |
| | PLACEMENT BUT WITHOUT THE FOOTER IDENTIFICATION TAG |
| | WHICH IS TO BE INSTALLED? 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 4) THE SAME HOLD TRUE ABOUT THE VERTICAL REINFORCEMENT |
| | THERE ARE VARIOUS DETAILS BUT THEY DO NOT PROVIDE THEY |
| | ARE TO BE USED AS PART OF THE DUMPSTER ENCLOSURE |
| | DETAILS. SIZE OF STEEL, PLACEMENT OF STEEL LAP FROM THE |
| | FOUNDATION ARE NOT GIVEN IN THE DETAILS (IDENTIFICATION |
| | MARKERS). 107.2.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | 2017 FBC-B 2103.4 REINFORCEMENT FOR CMU. |
| | |
| | 5) THE SHEET 333A DETAIL 6 NOTES THE DOUBLE GATES ARE |
| | TO BE 13 FEET WIDE BY 5 FEET HIGH LOUVERED ALUMINUM |
| | GATES ON 2X2 ALUMINUM TUBE. WITHIN THE FILE FOLDER IS A |
| | MIAMI-DADE NOA 19-0731.04 LOUVERED DOOR PRODUCT |
| | APPROVAL, IS THERE TO BE A DOOR TO BE CUT INTO ONE OF |
| | THE SIDE WALLS? 107.2.1.2 AGAIN ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| | TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |