| 2019-12-17 11:39:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET 319A - THERE IS AN INDICATION OF DRY STORAGE |
| | UNDER THE SOUTH STAIR. THGERE IS NO STAIR DETAIL |
| | INDICATING THE REQUIRED SEPARATION OF THE STARIWELL. |
| | |
| | PER NFPA 101. |
| | |
| | 7.2.2 STAIRS. |
| | 7.2.2.1 GENERAL. |
| | 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF |
| | EGRESS SHALL |
| | CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND |
| | TO THE |
| | SPECIAL REQUIREMENTS OF 7.2.2, UNLESS OTHERWISE |
| | SPECIFIED IN |
| | 7.2.2.1.2. |
| | |
| | 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| | 7.2.2.5.1 ENCLOSURES. |
| | 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| | EXIT COMPONENT |
| | SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2. |
| | |
| | 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN |
| | EXIT |
| | ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER STAIRS, |
| | UNLESS |
| | OTHERWISE PERMITTED BY 7.2.2.5.3.2. |
| | |
| | 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED |
| | UNDER STAIRS, |
| | PROVIDED THAT BOTH ALL OF THE FOLLOWING CRITERIA ARE |
| | MET: |
| | (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR |
| | ENCLOSURE BY THE |
| | SAME FIRE RESISTANCE AS THE EXIT ENCLOSURE. |
| | (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE |
| | FROM |
| | WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.) |
| | (3) THE SPACE IS NOT USED FOR THE STORAGE OF |
| | COMBUSTIBLE OR |
| | FLAMMABLE LIQUIDS, OR OTHERWISE HAZARDOUS MATERIALS. |
| | |
| | PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF |
| | CONSTRUCTION. |
| | |
| | |
| | 2) SHEET 319 A - THE NORTH STAIR DOES NOT INDICATE THE |
| | REQUIRED SEPARATION DETAIL AS NOTED IN # 1 ABOVE. |
| | |
| | PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF |
| | CONSTRUCTION. |
| | |
| | |
| | |
| | 3) SHEET 319 A - THE IS A STAGE INDICATED. |
| | |
| | THERE ARE NO INDICATION OF THE CONSTRUCTION FEATURES OF |
| | THE STAGE. |
| | |
| | PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF |
| | CONSTRUCTION. |
| | |
| | |
| | |
| | 4) SHEET 320 A - THERE ARE NO INDICATIONS OF DOOR |
| | HARDWARE WITHIN THE DOOR SCHEDULE. |
| | |
| | PLEASE REVIEW AND PROVIDE PER THE APPLICABLE OCCUPANCY |
| | CODE. |
| | |
| | |
| | 5) SHEET 308 A - THERE IS AN INDICATION OF AN ASSEMBLY |
| | OCCUPNACY; HOWEVER, THERE ARE TWO RESIDENTIAL |
| | OCCUPANCIES. |
| | |
| | IS THIS A MIXED OR SEPARATED OCCUPANCY? |
| | |
| | PLEASE PROVIDE PER NFPA 101 CH 6, OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO |
| | OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE |
| | OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE |
| | OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED |
| | ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL, |
| | HORIZONTAL, OR |
| | BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED |
| | TO PROVIDE |
| | COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE |
| | BUILDING. |
| | 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING |
| | SHALL COMPLY |
| | WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN. |
| | |
| | PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF |
| | CONSTRUCTION. |
| | |
| | |
| | 6) SHEET 336 A - THE THREE MAIN EXIT DOORS TO THE |
| | ASSEMBLY AREA SHOW HARDWARE SET # 6. RIM CYLINDER, |
| | MORTISE DEVICE AND FLOOR STOP. |
| | |
| | THESE MAY NOT BE COMPLIANT WITH THE REQUIRED EXIT |
| | HARDWARE, PER NFPA 101, CH 12 & CH 7. |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS |
| | PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS |
| | AS PERMITTED IN 12.2.2.2.6. |
| | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| | SHALL BE PERMITTED |
| | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| | IF BOTH OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY |
| | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY |
| | OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| | RELEASED |
| | BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | |
| | 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE. |
| | 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE |
| | EQUIPPED WITH |
| | PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET |
| | ALL OF THE |
| | FOLLOWING CRITERIA: |
| | (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE |
| | ACTUATING |
| | PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF |
| | OF THE |
| | WIDTH OF THE DOOR LEAF. |
| | (2) IT SHALL BE MOUNTED AS FOLLOWS: |
| | (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN. |
| | (865 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30 |
| | IN. (760 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE |
| | NOT TO EXCEED |
| | 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND |
| | LATCHES. |
| | |
| | PLEASE REVIEW AND CORRECT OF PROVIDE CODE COMPLIANT |
| | JUSTIFICATION. |
| | |
| | |
| | 7) SHEET 319 A - THERE IS AN INDICATION OF A STAGE AND |
| | BAR IN THIS ASSEMBLY OCCUPANCY AND COULD BE CONSIDERED |
| | A NIGHCLUB |
| | |
| | PER NFPA 101, CH 12 |
| | |
| | 12.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 12.3.5.1 THE WHERE THE OCCUPANT LOAD EXCEEDS 100, THE |
| | FOLLOWING |
| | ASSEMBLY OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY |
| | AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH 9.7.1.1(1): |
| | (1) DANCE HALLS |
| | (2) DISCOTHEQUES |
| | (3) NIGHTCLUBS |
| | (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING |
| | |
| | PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION OF JUSTIFY |
| | WITH DETAILED NARRATIVE AND CODE REFERNCES. |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |