| 2019-10-10 08:40:41 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1- PERMIT APPLICANT IS A CERTIFIED RESIDENTIAL |
| | CONTRACTOR. BASED ON THE SCOPE OF WORK LIMITS OF SEC. |
| | 489.105 (3)(C) FLORIDA STATUTES A RESIDENTIAL |
| | CONTRACTOR CAN NOT PERFORM WORK IN THIS MULTISTORY |
| | CONDOMINIUM. SEE COPY OF THIS SECTION BELOW. NEED |
| | CONTRACTOR WHO CAN PERFORM THE WORK IN THIS BUILDING. |
| | |
| | |
| | SEC. 489.105 (3)(C): "RESIDENTIAL CONTRACTOR" MEANS A |
| | CONTRACTOR WHOSE SERVICES ARE LIMITED TO CONSTRUCTION, |
| | REMODELING, REPAIR, OR IMPROVEMENT OF ONE-FAMILY, |
| | TWO-FAMILY, OR THREE-FAMILY RESIDENCES NOT EXCEEDING |
| | TWO HABITABLE STORIES ABOVE NO MORE THAN ONE |
| | UNINHABITABLE STORY AND ACCESSORY USE STRUCTURES IN |
| | CONNECTION THEREWITH. |
| | |
| | 2- SOUND INSULATION UNDERLAYMENT TEST RESULTS |
| | SUBMITTED; |
| | |
| | A) FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX TEST |
| | SUBMITTED IS FOR UNDERLAYMENT USED WITH PORCELAIN |
| | TILES. NEED COPY OF TEST FOR ASSEMBLY THAT MATCHES |
| | PROPOSED INSTALLATION. THE PROPOSED INSTALLATION IS |
| | ENGINEERED WOOD FLOORING. |
| | SEC. 720.1 OF FBC 6TH EDITION (2017). |
| | |
| | B) SOUND TRANSMISSION CLASS (STC) TEST SUBMITTED IS FOR |
| | UNDERLAYMENT USED WITH PORCELAIN TILES. NEED COPY OF |
| | TEST FOR ASSEMBLY THAT MATCHES PROPOSED INSTALLATION. |
| | THE PROPOSED INSTALLATION IS ENGINEERED WOOD FLOORING. |
| | SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| | |
| | C) IMPACT INSULATION CLASS (IIC) TEST SUBMITTED IS FOR |
| | UNDERLAYMENT USED WITH PORCELAIN TILES. NEED COPY OF |
| | TEST FOR ASSEMBLY THAT MATCHES PROPOSED INSTALLATION. |
| | THE PROPOSED INSTALLATION IS ENGINEERED WOOD FLOORING. |
| | SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| | |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND |
| | PROPOSED FLOOR FINISH. ALSO, THERE ARE TESTS FOR 6" OR |
| | 8" CONCRETE SLABS WITH OR WITHOUT ACOUSTICAL CEILING. |
| | TYPICALLY THERE ARE NOT SUSPENDED ACOUSTICAL CEILINGS |
| | IN THESE BUILDINGS |
| | |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |