2019-10-10 08:40:41RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- PERMIT APPLICANT IS A CERTIFIED RESIDENTIAL
 CONTRACTOR. BASED ON THE SCOPE OF WORK LIMITS OF SEC.
 489.105 (3)(C) FLORIDA STATUTES A RESIDENTIAL
 CONTRACTOR CAN NOT PERFORM WORK IN THIS MULTISTORY
 CONDOMINIUM. SEE COPY OF THIS SECTION BELOW. NEED
 CONTRACTOR WHO CAN PERFORM THE WORK IN THIS BUILDING.
  
  
 SEC. 489.105 (3)(C): "RESIDENTIAL CONTRACTOR" MEANS A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO CONSTRUCTION,
 REMODELING, REPAIR, OR IMPROVEMENT OF ONE-FAMILY,
 TWO-FAMILY, OR THREE-FAMILY RESIDENCES NOT EXCEEDING
 TWO HABITABLE STORIES ABOVE NO MORE THAN ONE
 UNINHABITABLE STORY AND ACCESSORY USE STRUCTURES IN
 CONNECTION THEREWITH.
  
 2- SOUND INSULATION UNDERLAYMENT TEST RESULTS
 SUBMITTED;
  
 A) FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX TEST
 SUBMITTED IS FOR UNDERLAYMENT USED WITH PORCELAIN
 TILES. NEED COPY OF TEST FOR ASSEMBLY THAT MATCHES
 PROPOSED INSTALLATION. THE PROPOSED INSTALLATION IS
 ENGINEERED WOOD FLOORING.
 SEC. 720.1 OF FBC 6TH EDITION (2017).
  
 B) SOUND TRANSMISSION CLASS (STC) TEST SUBMITTED IS FOR
 UNDERLAYMENT USED WITH PORCELAIN TILES. NEED COPY OF
 TEST FOR ASSEMBLY THAT MATCHES PROPOSED INSTALLATION.
 THE PROPOSED INSTALLATION IS ENGINEERED WOOD FLOORING.
 SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) IMPACT INSULATION CLASS (IIC) TEST SUBMITTED IS FOR
 UNDERLAYMENT USED WITH PORCELAIN TILES. NEED COPY OF
 TEST FOR ASSEMBLY THAT MATCHES PROPOSED INSTALLATION.
 THE PROPOSED INSTALLATION IS ENGINEERED WOOD FLOORING.
 SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
  
 NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND
 PROPOSED FLOOR FINISH. ALSO, THERE ARE TESTS FOR 6" OR
 8" CONCRETE SLABS WITH OR WITHOUT ACOUSTICAL CEILING.
 TYPICALLY THERE ARE NOT SUSPENDED ACOUSTICAL CEILINGS
 IN THESE BUILDINGS
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  