| Notes |
| Date |
Text |
| 2020-01-08 18:26:38 | RESIDENTIAL (R3), RE-ROOF THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1-OK | | | | | | ORIGINAL COMMENT: | | | 2- FLAT ROOF NOA 18-0919.07 SUBMITTED: SELECTED | | | ASSEMBLY ON PAGE 21 OF 27 DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED | | | RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER | | | AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7 | | | ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE | | | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | REPEAT COMMENT. RAS 117 CALCULATIONS SUBMITTED ARE DONE | | | FOR NOA 18-1127.18. THIS DOESN'T MATCH NOA 18-0919.07 | | | SUBMITTED BY THE ROOFING CONTRACTOR. THESE ARE TWO | | | DIFFERENT MANUFACTURERS. REVISE AS REQUIRED TO MATCH | | | AND PROVIDE TWO COPIES. ONLY ONE COPY WAS PROVIDED THIS | | | TIME. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|