| 2019-10-10 17:11:54 | RESIDENTIAL (R3), RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER, |
| | THE VALUE OF THE STRUCTURE IS $350.151. THEREFORE, NEED |
| | TO COMPLY WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED |
| | BY SEC. 706.8 FBC-EXISTING BUILDING. SHOW COMPLIANCE. |
| | NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOF TO |
| | WALL CONNECTIONS. THIS WORK CAN NOT BE DONE BY THE |
| | ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSESSES |
| | THE PROPER LICENSE TO PERFORM THIS WORK. |
| | |
| | 2- FLAT ROOF NOA 18-0919.07 SUBMITTED: SELECTED |
| | ASSEMBLY ON PAGE 21 OF 27 DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED |
| | RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER |
| | AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7 |
| | ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE |
| | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- ASPHALT SHINGLES ROOF PITCH OF 2:12 TO LESS THAN |
| | 4:12 REQUIRES TWO LAYERS OF UNDERLAYMENT AS REQUIRED BY |
| | SEC. R905.2.2 FBC-RESIDENTIAL. |
| | |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |