| 2019-11-21 14:40:15 | 1) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION |
| | STATES" REMODEL MASTER BATH" YET GAS PLANS HAVE BEEN |
| | SUBMITTED. CLARIFY. REVISE THE DESCRIPTION OF WORK ON |
| | THE PERMIT APPLICATION.THE APPLICATION SHALL CLEARLY |
| | REFLECT THE SCOPE OF WORK TO BE PERFORMED. WPB AMEND. |
| | TO FBC SEC. 107.2.1.2ND REQUEST. |
| | 2) WHAT SIZING TABLE IS BEING USED FOR THE LOW PRESSURE |
| | SYSTEM. THE PLANS REFER TO TABLE 402.4(5) FOR PIPING IN |
| | WALLS. THIS TABLE IS FOR A 2 PSI SYSTEM YET THE GAS |
| | PLAN SHOW THIS AS LOW PRESSURE PIPING. CLARIFY. |
| | 3) SIZE THE PIPING DDOWNSTREAM OF THE REGULATOR FOR THE |
| | EXTERIOR TANKLESS WATER HEATER, AND THE POOL HEATER. |
| | 4) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN |
| | SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND |
| | THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. THE |
| | LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH |
| | THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 5) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE |
| | LOCATION OF ALL OF THE GAS APPLICANCES. |
| | 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE STOVE |
| | AND THE DRYER PER THE 2017 FBC-RES. SEC.G 2407.1 AND |
| | G2439.4 (CLOTHES DRYERS). 2ND REQUEST. |
| | |