| 2019-10-22 04:55:16 | 1) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION |
| | STATES" REMODEL MASTER BATH" YET GAS PLANS HAVE BEEN |
| | SUBMITTED. CLARIFY. REVISE THE DESCRIPTION OF WORK ON |
| | THE PERMIT APPLICATION. |
| | 2) THE GAS PLAN NOTES A 2 PSI SYSTEM BUT THE TABLES |
| | REFERENCED ON THE GAS DRAWING ARE FOR LESS THAN A 2 PSI |
| | SYSTEM. CLARIFY. |
| | 3) THE PERMIT APPLICATION NOTES THE JOB ADDRESS AS 233 |
| | RILYN DR. BUT THE GAS PLAN HAS THE ADDRESS AS 235 RILYN |
| | DR. CLARIFY. |
| | 4) IF THIS IS A 2 PSI SYSTEM, SHOW THE LOCATION OF ALL |
| | REGULATORS AND SHOW THE DISTANCE FROM EACH REGULATOR TO |
| | THE FURTHEST OUTLET ON THAT BRANCH LINE. |
| | 5) CLEARLY SHOW ALL PIPE SIZES ON THE GAS DRAWING, SOME |
| | OF THE SIZES ARE DIFFICULT TO READ. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | STOVE, THE DRYER, AND FOR THE TANKLESS WATER HEATER IF |
| | IT IS NOT LOCATED ON THE EXTERIOR OF THE BUILDING PER |
| | THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES |
| | DRYERS) OR 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 |
| | (CLOTHES DRYERS). |
| | 7) SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. |
| | 8) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN |
| | SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND |
| | THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. THE |
| | LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH |
| | THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 9) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | 10) A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL |
| | GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420. |
| | 11) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE |
| | INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE MP |
| | REGULATOR. 2017 FBC-FUEL GAS SEC. 410.2 (7). |
| | 12) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE |
| | LOCATION OF ALL OF THE GAS APPLICANCES. |
| | 13) A YELLOW INSULATED COPPER TRACER WIRE OR OTHER |
| | APPROVED CONDUCTOR SHALL BE INSTALLED ADJACENT TO |
| | UNDERGROUND NONMETALLIC PIPING. THE WIRE SHALL NOT BE |
| | IN CONTACT WITH HE NONMETALLIC PIPE. 2017 FBC-FUEL GAS |
| | SEC.404.17.3. |
| | |
| | ***NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE AT |
| | THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | ***NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE AT |
| | THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | |
| | |
| | |