| 2019-10-23 11:51:13 | 1ST REVIEW: 19100411 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHOW LOCATION OF WATER HEATER AND PLUMBING FIXTURES | | | ON FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. WHAT PLUMBING WORK IS BEING DONE IN THE | | | BATHROOMS.PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. WHAT TYPE OF WATER HEATER IS BEING INSTALLED IS IT | | | THE SAME AS EXISTING.PER WPB AMEND TO FBC 107.2.1 | | | | | | 4. PLEASE ENLARGE FLOOR PLAN . BUILDING PLANS SHALL BE | | | DRAWN TO A MINIMUM 1/8 | | | INCH SCALE UPON SUBSTANTIAL PAPER, PER WPB AMEND TO FBC | | | 107.2.1.3 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|