| 2019-10-17 16:58:06 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1.SHT. A-250 THE GRAB BARS SHALL BE MEASURED FROM |
| | FINISHED FLOOR TO THE TOP OF THE GRIPPING SURFACE NOT |
| | TO THE CENTER OF THE BAR AS SHOWN ON PLAN. PER FBC ACC |
| | 609.4 |
| | |
| | 2. PLEASE LABEL CLEAR FLOOR FOR THE TOILET LAVATORY AND |
| | WATER FOUNTAIN. PER FBC PL 604.3.1, 606.2, 602.2 |
| | |
| | 3. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. PER |
| | FBC PL 604.4 |
| | |
| | 4. THE BREAK ROOM SINK AND AT LEAST ONE OF THE |
| | PROCEDURE ROOM SINKS SHALL COMPLY WITH FBC ACC 212.2, |
| | 212.3, 606.2, 606.3, 804.4 |
| | |
| | 5. SHT. P-000 NOTE #29 HOT WATER PIPING SHALL COMPLY |
| | WITH FBC ENERGY 2017 6TH EDITION |
| | |
| | 6. SHT. P-102 PLACE NOTE ON PLAN THE SANITARY VENT |
| | SHALL A MIN OF 10' AWAY OF ANY AIR INTAKES OR OPENINGS. |
| | PER FBC PL 903.5 |
| | |
| | 7. THE PLUMING SCHEDULE LIST FLOOR MOUNTED TOILETS AND |
| | THE SANITARY ISOMETRIC SHOWS WALL MOUNTED PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHT. P-500 P-501, P-000 REMOVE ALL REFERENCES TO |
| | DIVISION 22 THE GOVERNING CODE SHALL BE LISTED ON THE |
| | PLAN AS FLORIDA BUILDING CODE PLUMBING 2017 6TH |
| | EDITION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |