| Date |
Text |
| 2019-10-18 13:04:54 | 1. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | 2. PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| | 3. ENGINEERED FIRE ALARM AND FIRE SPRINKLER |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL |
| | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN |
| | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. |
| | 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | 5. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A |
| | MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL |
| | LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE |
| | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT |
| | LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, |
| | NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF |
| | EGRESS AT FLOOR LEVEL. |
| | |
| | S.THOMAS |
| | 561-804-4728 |