2019-10-16 15:56:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE COVERSHEET A-000 WAS NOT DIGITALLY SIGNED BY THE
 ARCHITECT. FAC 61G1-16.003
  
 2) THE DEMOLITION PLAN A-100 IS LISTED IN THE PLAN
 INDEX BUT IS MISSING FROM THE SUBMITTAL. FBC 107.2.1
  
 3) ELEVATION #7 ON A-250 HAS A DIMENSION FOR THE
 BREAK-ROOM SINK AS 3'-0". FBC ACCESSIBILITY SECTION
 606.3 REQUIRES THE HIGHER OF THE SINK RIM OR COUNTER
 TOP TO BE A MAXIMUM OF 34".
  
 4) FBC ACCESSIBILITY SECTION 904.4.1 FOR A PARALLEL
 APPROACH REQUIRES A PORTION OF THE SERVICE COUNTER AT
 THE RECEPTION DESK TO BE A MINIMUM OF 36" IN LENGTH.
 DETAIL 15 ON A-250 SPECIFIES 34.5".
  
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.