| Plan Review Notes For Permit 19100398 |
| Permit Number |
19100398 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-16 15:56:10 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE COVERSHEET A-000 WAS NOT DIGITALLY SIGNED BY THE | | | ARCHITECT. FAC 61G1-16.003 | | | | | | 2) THE DEMOLITION PLAN A-100 IS LISTED IN THE PLAN | | | INDEX BUT IS MISSING FROM THE SUBMITTAL. FBC 107.2.1 | | | | | | 3) ELEVATION #7 ON A-250 HAS A DIMENSION FOR THE | | | BREAK-ROOM SINK AS 3'-0". FBC ACCESSIBILITY SECTION | | | 606.3 REQUIRES THE HIGHER OF THE SINK RIM OR COUNTER | | | TOP TO BE A MAXIMUM OF 34". | | | | | | 4) FBC ACCESSIBILITY SECTION 904.4.1 FOR A PARALLEL | | | APPROACH REQUIRES A PORTION OF THE SERVICE COUNTER AT | | | THE RECEPTION DESK TO BE A MINIMUM OF 36" IN LENGTH. | | | DETAIL 15 ON A-250 SPECIFIES 34.5". | | | | | | 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. |
|