2019-10-17 13:51:07PROVISO:
  
 1. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2. PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3. PER NFPA 241 SECTION 8.6.2 TEMPORARY SEPARATION
 WALLS: PROTECTION SHALL BE PROVIDED TO SEPARATE AN
 OCCUPIED PORTION OF THE STRUCTURE FROM A PORTION OF THE
 STRUCTURE UNDERGOING ALTERATION, CONSTRUCTION, OR
 DEMOLITION OPERATIONS WHEN SUCH OPERATIONS ARE
 CONSIDERED AS HAVING A HIGHER LEVEL OF HAZARD THAN THE
 OCCUPIED PORTION OF THE BUILDING. WALLS SHALL HAVE AT
 LEAST A 1-HOUR FIRE RESISTANCE RATING. OPENING
 PROTECTIVES SHALL HAVE AT LEAST A 45-MINUTE FIRE
 PROTECTION RATING. NONRATED WALLS AND OPENING
 PROTECTIVES SHALL BE PERMITTED WHEN AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM IS INSTALLED.
  
 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  