| Date |
Text |
| 2019-10-24 12:53:28 | NFIP REVIEW ? BUILDING UNDER CONSTRUCTION EC |
| | |
| | SUBMITTAL# 19100325 |
| | MASTER PERMIT# 18090744 |
| | |
| | ADDRESS ? 2305 S FLAGLER DR |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW ? MAIN RESIDENCE EC |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PLEASE MAKE THE FOLLOWING CHANGES TO THE BUILDING UNDER |
| | CONSTRUCTION ELEVATION CERTIFICATE PER FEMA ELEVATION |
| | CERTIFICATE INSTRUCTIONS, 2015 EDITION |
| | |
| | 1. A9 (A) ? CHANGE SQ. FOOTAGE OF ATTACHED GARAGE FROM |
| | 880 TO 1750 SQ. FT. |
| | (67.3FT. X 26 FT.) |
| | 2. A9 (B) ? STATE NUMBER OF FLOOD OPENINGS. TOP OF |
| | GARAGE SLAB IS AT 7.9 FEET NAVD88. THIS IS BELOW DFE. |
| | FLOOD VENTS REQUIRED. |
| | 3. A9 ( C ) - STATE NET AREA OF FLOOD OPENINGS |
| | 4. A9 (D) ? NON-ENGINEERED OPENINGS SELECTED. PROVIDE |
| | DETAIL. |
| | 5. C2 (A) ? TOP OF BOTTOM FLOOR STATED AT 8.9 FEET. |
| | PROVIDE COMMENT IN SECTION D THAT THIS ELEVATION WILL |
| | BE AT OR ABOVE DFE OF 9.0 FEET NAVD88 AT FINISHED |
| | CONSTRUCTION. |
| | 6. C2 (E) ? ENTRY OF N/A. PROVIDE COMMENT IN SECTION D |
| | THAT LOWEST ELEVATION OF MACHINERY OR EQUIPMENT SHALL |
| | BE AT OR ABOVE DFE OF 9.0 FEET NAVD88 AT FINISHED |
| | CONSTRUCTION. |
| | 7. SECTION D ? SEE COMMENTS UNDER SIGNATURE AND SEAL |
| | REVIEW. |
| | |
| | 1ST REVIEW ? ACCESSORY STRUCTURE EC ? GYM |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PLEASE MAKE THE FOLLOWING CHANGES TO THE BUILDING UNDER |
| | CONSTRUCTION ELEVATION CERTIFICATE PER FEMA ELEVATION |
| | CERTIFICATE INSTRUCTIONS, 2015 EDITION |
| | |
| | 1. A9 (A) ? THIS STRUCTURE DOES NOT HAVE AN ATTACHED |
| | GARAGE. ENTER 0. |
| | 2. C2 (A) ? TOP OF BOTTOM FLOOR STATED AT 8.9 FEET. |
| | PROVIDE COMMENT IN SECTION D THAT THIS ELEVATION WILL |
| | BE AT OR ABOVE DFE OF 9.0 FEET NAVD AT FINISHED |
| | CONSTRUCTION. |
| | 3. C2 (E) ? LOWEST ELEVATION OF MACHINERY OR EQUIPMENT |
| | STATED AS N/A. PROVIDE COMMENT IN SECTION D THAT LOWEST |
| | ELEVATION OF MACHINERY OR EQUIPMENT SHALL BE AT OR |
| | ABOVE DFE 9.0 FEET NAVD88. |
| | 4. SECTION D ? SEE COMMENTS UNDER SIGNATURE AND SEAL |
| | REVIEW. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |