| 2019-10-08 07:25:32 | 10/08/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON | | | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE | | | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 2. SUBMIT MANUFACTURER?S SPECIFICATION | | | SHEETS/INSTALLATION MANUAL FOR GENERATOR TO VERIFY | | | COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. | | | 3. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF | | | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. | | | 4. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 | | | FBC RES. SEC. G2419.2. 55. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|