| Plan Review Notes For Permit 19100269 |
| Permit Number |
19100269 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-28 09:17:22 | PLUMBING 1ST REVIEW**DENIED**19100269 | | | 1) PROVIDE HEATER PAN, PAN DRAIN, AND RELIEF DRAIN | | | DETAIL SHOWING THE RELIEF DISCHARGING INTO THE PAN AND | | | THE DRAIN DRAIN WITH MATERIAL TO BE USED DISCHARGING TO | | | THE OUTSIDE MIN 6? ABOVE GROUND. FBC 107.2 | | | 2) WASHING MACHINE STACK SHALL BE 3?. THE MIN SIZE IS | | | NOT REFERENCE IN THE RES PLB CODE THERE FORE FBCR-P2601 | | | REFERS TO THE PLB CODE. FBC-PLB 709.1 CALLS OUT | | | RESIDENTIAL WASHING MACHINES SHALL COMPLY WITH FOOT | | | NOTE G WHICH REFERS YOU TO FBC-PLB 406.2 WHICH CALLS | | | OUT ALL WASHING MACHINES BRANCH AND STACK LINE BE MIN | | | 3?. | | | TIM HUNT | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|