2019-10-28 09:17:22PLUMBING 1ST REVIEW**DENIED**19100269
 1) PROVIDE HEATER PAN, PAN DRAIN, AND RELIEF DRAIN
 DETAIL SHOWING THE RELIEF DISCHARGING INTO THE PAN AND
 THE DRAIN DRAIN WITH MATERIAL TO BE USED DISCHARGING TO
 THE OUTSIDE MIN 6? ABOVE GROUND. FBC 107.2
 2) WASHING MACHINE STACK SHALL BE 3?. THE MIN SIZE IS
 NOT REFERENCE IN THE RES PLB CODE THERE FORE FBCR-P2601
 REFERS TO THE PLB CODE. FBC-PLB 709.1 CALLS OUT
 RESIDENTIAL WASHING MACHINES SHALL COMPLY WITH FOOT
 NOTE G WHICH REFERS YOU TO FBC-PLB 406.2 WHICH CALLS
 OUT ALL WASHING MACHINES BRANCH AND STACK LINE BE MIN
 3?.