| 2020-01-17 15:46:18 | 5TH REVIEW FBC-2017 MECHANICAL | | | PERMIT #19100236 | | | 12/4/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: PLEASE PROVIDE AN AHRI CERTIFICATE FOR | | | THE NEW TRANE/MITSUBISHI SPLIT SYSTEM TO VERIFY IT IS A | | | MATCHING SYSTEM- SECTION R501.7 FBC EC. | | | | | | 2) M-1: THE AC SCHEDULE INDICATES THE AIR HANDLER WILL | | | PRODUCE 388 CFMS OF AIR, HOWEVER THE PLAN INDICATES AIR | | | DISTRIBUTION OF 514 CFMS, PLEASE CORRECT- SECTION | | | 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|