| 2019-12-17 15:55:26 | PLAN REVIEW - MECHANICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 4TH REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE AC PLAN LISTING |
| | MAKE AND MODEL OF THE SYSTEM, COOLING AND HEATING BTUH, |
| | AND CFM CAPACITY. PLEASE NOTE THAT THE CALCULATIONS ARE |
| | INDICATING 411 CFMS OF SUPPLY AIR, HOWEVER THE PLAN |
| | INDICATES 577 CFMS- SECTION 107.2.1 WPB. |
| | (PROPOSED EQUIPMENT ON PLAN IS A MITSUBISHI MODEL |
| | SUK-KA18NA MINI-SPLIT SYSTEM. PLAN SHOWS A DUCTED |
| | SYSTEM. PROVIDE EQUIPMENT THAT COMPLIES WITH THE |
| | DESIGN. MANUAL J SHALL LIST MAKE AND MODEL OF HEATING |
| | AND COOLING EQUIPMENT. BTUH AND CFM CAPACITY OF |
| | EQUIPMENT ON PLAN EXCEEDS SIZING LIMITATIONSOF DESIGN |
| | PER RE 403.7.1.1). |
| | |
| | 2) EXHAUST VEMTILATION AT A RATE OF 100 CFMS |
| | INTERMITTENT OR 25 CFMS CONTINOUS SHALL BE PROVIDED FOR |
| | THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE SECTION |
| | M1503.1 FOR RANGE HOOD REQUIRMENTS, AND M1503.4 FOR |
| | MAKEUP AIR. - CORRECTED |
| | |
| | 3) VERIFY COMPLIANCE WITH SECTION R403.3.6 AIR-HANDLING |
| | UNITS IN ATTICS: - CORRECTED |
| | |
| | AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC |
| | WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION |
| | R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR |
| | COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING |
| | CONDITIONS ARE MET: (405 SUBMITTED) |
| | |
| | 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| | 6 FEET (1829 MM) OF AN ATTIC ACCESS. (TO BE FEILD |
| | VERIFIED) |
| | |
| | 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN |
| | THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| | PROPERLY. (SEE DETAIL ON MECH. PLAN) |
| | |
| | 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| | REPLACE THE AIR HANDLER. (TO BE FEILD VERIFIED) |
| | |
| | 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| | INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| | CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST |
| | PARAGRAPH IN BOLD: (TO BE FEILD VERIFIED) |
| | |
| | NOTICE TO HOMEOWNER |
| | A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR |
| | HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT |
| | AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM, |
| | YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. |
| | YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR |
| | BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU |
| | WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR |
| | (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE |
| | CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL |
| | DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF |
| | SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER |
| | WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF |
| | PEAK OPERATION. |
| | |
| | 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE |
| | CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS |
| | M1305.1.4.1 AND M1401.4 FBC RES. - (NOT ADDRESSED) |
| | (M1411.8 LOCKING ACCESS PORT CAPS) |
| | |
| | NEW COMMENT |
| | |
| | 5) E3901.12 HVAC OUTLET. |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) |
| | OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED |
| | TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING |
| | MEANS. (210.63) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |