Plan Review Notes
Plan Review Notes For Permit 19100236
Permit Number 19100236
Review Stop M
Sequence Number 3
Notes
Date Text
2019-12-04 07:55:333RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19100236
 12/4/2019
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE ARCHITECT OF RECORD HAS NOT RESPONDED TO THE 1ST
 REVIEW COMMENTS. HE HAS STATED IN HIS RESPONSE
 NARRATIVE THAT RESPONSES ARE TO BE PROVIDED BY AC
 SUB-CONTRACT. PLEASE NOTE THAT ALL PLANS SHALL BE
 SUBMITTED UNDER THE MAIN PERMIT, UNLESS MECHANICAL IS
 TO BE COMPLETELY EXCLUDED FROM THE MAIN PERMIT, AND A
 SEPARATE PRIMARY PERMIT IS PULLED FOR MECHANICAL.
 PLEASE REQUEST THE ARCHITECT TO PROVISDE PLANS AND
 SPECIFICATIONS IN RESPONSE TO THE 1ST REVIEW COMMENTS
 LISTED BELOW.
  
 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE AC PLAN LISTING
 MAKE AND MODEL OF THE SYSTEM, COOLING AND HEATING BTUH,
 AND CFM CAPACITY. PLEASE NOTE THAT THE CALCULATIONS ARE
 INDICATING 411 CFMS OF SUPPLY AIR, HOWEVER THE PLAN
 INDICATES 577 CFMS- SECTION 107.2.1 WPB.
  
 2) EXHAUST VEMTILATION AT A RATE OF 100 CFMS
 INTERMITTENT OR 25 CFMS CONTINOUS SHALL BE PROVIDED FOR
 THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE SECTION
 M1503.1 FOR RANGE HOOD REQUIRMENTS, AND M1503.4 FOR
 MAKEUP AIR.
  
 3) VERIFY COMPLIANCE WITH SECTION R403.3.6 AIR-HANDLING
 UNITS IN ATTICS:
  
 AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
  
 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN
 THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1 AND M1401.4 FBC RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  