Plan Review Notes
Plan Review Notes For Permit 19100236
Permit Number 19100236
Review Stop P
Sequence Number 1
Notes
Date Text
2019-10-30 06:05:39PLUMBING 1ST REVIEW**DENIED**19100236
 1) PLEASE CLARIFY WHICH WATER HEATER YOU ARE USING. THE
 R405/2017 CALLS OUT CONVENTIONAL 40 GALLON STORAGE
 TANK, SHT.EP-1 NOTE #22 CALL OUT A.O SMITH GPD-75 (
 POWER VENT GAS STORAGE TANK), AND THE FLOOR PLAN SHOW
 GAS TANKLESS WATER HEATER. PLEASE CLARIFY. ALSO IF NOT
 THE UNIT CALLED OUT IN THE R405/2017 YOU WILL NEED TO
 CORRECT AND RESUBMIT. IF A GAS HEATER IS CHOSEN A GAS
 PERMIT AND COMPLETE GAS ISOMETRIC TO INCLUDE ANY AND
 ALL EXISTING BTU?S ON THE SYSTEM, MATERIAL. ETC. FBC
 107.3.5
 2) KITCHEN IS DISCHARGING INTO THE BATHROOM GROUP WET
 VENT. THE KITCHEN SHALL DISCHARGE DOWNSTREAM. FBCR-P
 3108.1
 3) ONLY 1 WET VENT FIXTURE IS PERMITTED BEYOND THE
 BATHROOM GROUP VENT. FBCR-P3108.22
 4) THESE PLANS LACK THE REQUIRED SIGN AND SEAL BY THE
 DESIGN PROFESSIONAL REQUIRED BY 61G1.16005
 5) PROVIDE BATHROOM DIMENSIONS. FBC 107.2
  
 TIM HUNT
 CITY OF WEST PALM BEACH ( CGA SOLUTIONS)
 [email protected]
 561-248-2703
  