| Plan Review Notes For Permit 19100217 |
| Permit Number |
19100217 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2020-01-29 10:22:43 | BUILDING REVIEW APPROVED WITH PROVISO: | | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | | INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | 1- REVISE ENERGY CALCULATIONS: | | | (A) PROVIDE CORRECT JURISDICTION NUMBER (604700). | | | (B)REVISE DOOR INFORMATION PAGE 3 OF 4. DOOR NOA | | | 17-1212.10 SUBMITTED IS FOR GLAZED DOOR. THIS DOOR | | | NEEDS TO BE IN WINDOW GLAZING AREA. SEC. R405.5.3.3 | | | FBC-ENERGY CONSERVATION. | | | (C) REVISE OVERHANG DEPTH AND SEPARATION OF WINDOW | | | LOCATED ON THE NORTH SIDE. SEE PLANS AND REVISE AS | | | REQUIRED. . | | | | | | 2- DOOR NOA 17-1212.10 DON'T HAVE IMPACT GLAZING. | | | PROVIDE SHUTTERS PRODUCT APPROVAL (2 COPIES) AND | | | COMPLETE INSTALLATION SCHEDULE. | | | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, | | | WINDOWS, SHINGLES, SHUTTERS). | | | | | | 4- REVISE AND RE-SUBMIT TRUSS PACKAGE: | | | (A)TRUSS ENGINEER TO REVISE THE TRUSS DESIGN CRITERIA. | | | BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". SEE PLANS | | | AND REVISE AS REQUIRED. | | | (B)ENGINEER OF RECORD NEED TO REVIEW AND APPROVED THE | | | TRUSS PACKAGE BEFORE SUBMITTAL. | | | |
|