| | 01/16/2020 MET WITH MIRIAM. TOLD HER I NEED THE SECOND |
| | COPY OF DRAWING M.1 IN ORDER TO APPROVE MECHANICAL |
| | REVIEW WITH THE PROVISO. ONLY ONE COPY WAS SUBMITTED. |
| | |
| | |
| | RESIDENTIAL (R3) ADDITION FOURTH MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE COMPLETE INFORMATION FOR THE MECHANICAL WORK |
| | (LOAD CALCULATIONS AND PLANS). SEC. 1101.1 FBC-EXISTING |
| | BUILDING AND SEC. R403.7 FBC-ENERGY CONSERVATION. |
| | NOTE: SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL AS |
| | REQUIRED BY SEC. R403.7.1 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | A) EQUIPMENT LOAD CALCULATIONS SUBMITTED ARE DONE BASED |
| | ON THE FRONT DOOR FACING SOUTH. THIS IS INCORRECT. |
| | CALCULATIONS NEED TO BE DONE BASED ON THE ACTUAL |
| | ORIENTATION OF THE BUILDING AS REQUIRED BY SEC. |
| | R403.7.1 FBC-ENERGY CONSERVATION. THE MAIN ENTRY DOOR |
| | IS FACING EAST. REVISE AS REQUIRED. NOTE: COORDINATE |
| | WITH COMMENTS DONE ON THE ENERGY CALCULATIONS UNDER THE |
| | BUILDING REVIEW COMMENTS. |
| | |
| | B) DRAWING M.1 SUBMITTED. REVISE THE NORTH ORIENTATION |
| | ARROW TO MATCH PLANS AND SURVEY |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |