| Date |
Text |
| 2019-11-20 18:33:47 | RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5 |
| | FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | 2- OK. |
| | 3- OK. |
| | 4-OK. |
| | 5-OK |
| | 6- OK |
| | |
| | ORIGINAL COMMENT: |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR THE HURRICANE SHUTTERS SINCE WINDOW |
| | NOA 17-1212.19 AND DOOR NOA 17-1212.10 DON'T HAVE |
| | IMPACT GLAZING. |
| | PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 |
| | FBC-RESIDENTIAL AND SEC. 1101.1 FBC-EXISTING BUILDING |
| | NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE |
| | INSTALLATION SCHEDULE AS REQUIRED BY CITY |
| | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT |
| | PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY |
| | SAMPLE |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. THIS MAY BE A PROVISO AND CONTRACTOR MAY |
| | SUBMIT AFTER THE PERMIT IS APPROVED BUT BEFORE |
| | INSPECTIONS. |
| | |
| | ORIGINAL COMMENT: |
| | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, |
| | WINDOWS, SHINGLES, SHUTTERS) AS REQUIRED BY SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | 9- IMPACT FEES - |
| | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK |
| | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. |
| | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT |
| | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 10-OK. |
| | |
| | NOTE: |
| | TRUSS PACKAGE SUBMITTED NOTES: |
| | 1)TRUSS ENGINEER TO REVISE THE TRUSS DESIGN CRITERIA. |
| | BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". |
| | 2)ENGINEER OF RECORD NEED TO REVIEW AND APPROVED THE |
| | TRUSS PACKAGE. |
| | 3)SUBMIT REVISED TRUSS PACKAGE TO BUILDING INSPECTOR A |
| | T TIME OF FRAMING INSPECTION. |
| | |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |