Plan Review Notes
Plan Review Notes For Permit 19100217
Permit Number 19100217
Review Stop B
Sequence Number 2
Notes
Date Text
2019-11-20 18:33:47RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 2- OK.
 3- OK.
 4-OK.
 5-OK
 6- OK
  
 ORIGINAL COMMENT:
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE HURRICANE SHUTTERS SINCE WINDOW
 NOA 17-1212.19 AND DOOR NOA 17-1212.10 DON'T HAVE
 IMPACT GLAZING.
 PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2
 FBC-RESIDENTIAL AND SEC. 1101.1 FBC-EXISTING BUILDING
 NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE
 INSTALLATION SCHEDULE AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY
 SAMPLE
  
 RESPONSE:
 NOT ADDRESSED. THIS MAY BE A PROVISO AND CONTRACTOR MAY
 SUBMIT AFTER THE PERMIT IS APPROVED BUT BEFORE
 INSPECTIONS.
  
 ORIGINAL COMMENT:
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS,
 WINDOWS, SHINGLES, SHUTTERS) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 9- IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 10-OK.
  
 NOTE:
 TRUSS PACKAGE SUBMITTED NOTES:
 1)TRUSS ENGINEER TO REVISE THE TRUSS DESIGN CRITERIA.
 BUILDING IS LOCATED IN EXPOSURE "C" NOT "B".
 2)ENGINEER OF RECORD NEED TO REVIEW AND APPROVED THE
 TRUSS PACKAGE.
 3)SUBMIT REVISED TRUSS PACKAGE TO BUILDING INSPECTOR A
 T TIME OF FRAMING INSPECTION.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]