| 2019-10-23 18:40:45 | RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5 |
| | FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | SEC. R401.3 FBC-RESIDENTIAL. |
| | SEC. 107.2.5 CITY AMENDMENTS. |
| | SEC. 110.9 CITY AMENDMENTS. |
| | |
| | 3- THERE IS ONE WINDOW ON EXISTING BEDROOM #2 THAT IS |
| | GOING TO BE BLOCKED TO ALLOW FOR THE ADDITION. SPECIFY |
| | TYPE AND SIZE OF EXISTING WINDOW TO REMAIN ON THE SAME |
| | BEDROOM TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS. SEC. 1101.1 FBC-EXISTING BUILDING AND |
| | SEC. R310.2 FBC-RESIDENTIAL. |
| | NOTE: SIMILAR SITUATION APPLIES TO EXISTING BEDROOM #1. |
| | SPECIFY TYPE AND SIZE OF WINDOW TO REMAIN. |
| | |
| | 4- REVISE DESIGN CRITERIA SPECIFIED ON AT THE BOTTOM OF |
| | GENERAL NOTES ON SHEET 1 OF 2. |
| | THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT EXPOSURE |
| | "B". REVISE AS REQUIRED AND REVISE DOORS/WINDOWS DESIGN |
| | PRESSURES ACCORDINGLY. SEC. 1101.1 FBC-EXISTING |
| | BUILDING AND SEC. R301.2.1.4 FBC-RESIDENTIAL. |
| | |
| | 5- ROOF FRAMING PLAN SHOWN ON SHEET 2 OF 2: |
| | NEED TO SPECIFY TRUSS CONNECTOR FOR TRUSSES RESTING ON |
| | THE (2)2X10 LEDGER LOCATED ON THE EXISTING GABLE END |
| | THAT IS RECEIVING THE NEW TRUSSES. SEC. 1101.1 |
| | FBC-EXISTING BUILDING AND SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 6- EXTERIOR WALL SECTION ON SHEET 1 OF 2: |
| | A) ROOFING MATERIAL IS NOT CLEAR. EXISTING HOUSE AND |
| | PRODUCT APPROVAL SUBMITTED ARE FOR ROOF SHINGLES. THIS |
| | WALL SECTION SPECIFIED ROOF TILE. REVISE/CLARIFY AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) SPECIFY THE MIN. THICKNESS OF THE VAPOR BARRIER AS |
| | REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL AND SEC. |
| | 1101.1 FBC-EXISTING BUILDING. |
| | NOTE: THIS APPLIES TO THE SPECIFICATIONS ON THE |
| | FOUNDATION PLAN ALSO. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR THE HURRICANE SHUTTERS SINCE WINDOW |
| | NOA 17-1212.19 AND DOOR NOA 17-1212.10 DON'T HAVE |
| | IMPACT GLAZING. |
| | PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 |
| | FBC-RESIDENTIAL AND SEC. 1101.1 FBC-EXISTING BUILDING |
| | NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE |
| | INSTALLATION SCHEDULE AS REQUIRED BY CITY |
| | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT |
| | PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY |
| | SAMPLE |
| | |
| | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, |
| | WINDOWS, SHINGLES, SHUTTERS) AS REQUIRED BY SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9- IMPACT FEES - |
| | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK |
| | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. |
| | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT |
| | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 10-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S (APPLIES TO OWNER/BUILDER TOO) OVERHEAD |
| | AND PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY |
| | SEC. 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED TO |
| | $45,343. THE PERMIT FEE BALANCE IS $999.67 |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |