| 2020-05-13 16:03:18 | |
| | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT #19100015 |
| | 5/13/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A NEW ELECTRIC WATER HEATER IS SHOWN ON E1. PLEASE |
| | PROVIDE AN EQUIPMENT SCHEDULE ON THE PLUMBING PLAN |
| | INDICATING THE MAKE AND MODEL, GALLON SIZE, AND |
| | EFFICIENCY RATING- SEE TABLE C404.2 FBC EC. PLEASE |
| | INCLUDE THE COMPLIANCE DATA FOR THE UNIT IN THE ENERGY |
| | CALCULATION REPORT- SECTION R101.5 FBC EC. |
| | |
| | 2) SHEET S4 PLUMBING RISER DRAWING: |
| | A) NEW BATH #3- HORIZONTAL WET VENT: ONLY ONE OF THE |
| | TWO FIXTURE DRAINS- SHOWER OR WATER CLOSET- CAN BE |
| | LOCATED UPSTREAM OF THE DRY VENT CONNECTION AT THE |
| | LAVATORY DRAIN. THIS CAN BE CORRECTED BY SHOWING THE |
| | LAVATORY FIXTURE DRAIN CONNECTION BEING MADE BETWEEN |
| | THE SHOWER AND THE WATER CLOSET FIXTURE DRAINS- SECTION |
| | P3108.2.1 FBC RES. |
| | B) SHOW THE REQUIRED 2? VENT AND 3? BRANCH DRAIN FOR |
| | THE WASHING MACHINE- SECTION 406.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |