Plan Review Notes
Plan Review Notes For Permit 19100015
Permit Number 19100015
Review Stop M
Sequence Number 1
Notes
Date Text
2019-10-23 09:30:04RESIDENTIAL (R3) ALTERATION/ADDITION MECHANICAL REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SCOPE OF WORK ON SHEET D1 STATES THAT THERE IS NO
 MECHANICAL ON THIS PERMIT (MECHANICAL BY OTHERS).
 PROVIDE COMPLETE INFORMATION FOR THE MECHANICAL WORK
 (LOAD CALCULATIONS AND PLANS) OR PROVIDE COMPLETE
 INFORMATION UNDER A SEPARATE PERMIT. SEC. 105.1 CITY
 AMENDMENTS. SEC. 1101.1 FBC-EXISTING BUILDING AND SEC.
 R403.7 FBC-ENERGY CONSERVATION.
 NOTE: SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL AS
 REQUIRED BY SEC. R403.7.1 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved